IM-P707-01
CTLS Issue 1
71
SP8-10 Smart positioner
5.1.31 Menu: SW 2 Mask map
Menu/parameter
Value range
Description
Alarm Maintenan.
Alarm OoSpec.
Alarm Check Fct.
Alarm Failure
On, Off
When a general alarm is issued, an alarm current can
be sent via the Analogue position feedback. These
alarm groups are defined in accordance with Namur
NE107. Each individual group can be activated.
-
Alarm Maintenan. - Maintenance needed
-
Alarm OoSpec. - Operation outside specifications
-
Alarm Check Fct. - Functional test needed
-
Alarm Failure - Errors
Switch 1 Sim.
On, Off
Use this parameter to simulate the switch function.
-
Off - Simulation deactivated
5.1.32 Menu: Switch 2
Menu/parameter
Value range
Description
Switch 2 Funct.
Position Info
Diagnostic State
Use this parameter to select whether the switch is to
be used as a limit signal generator or for signaling
diagnostics messages.
-
Position Info - Evaluate position
-
Diagnostic State - Assess diagnosis status
Switch 2 Value
0 to 100%
Use this parameter to configure the position value as a
limit signal generator. It is taken into account when the
‘Switch 2 Funct.’ parameter is set to ‘Position Info’.
Switch 1 Logic
Active High
Active Low
Use this parameter to select the contact logic.
-
Active High (active) - Output current I > 2.1 mA
-
Active Low (active) - Output current I < 1.2 mA
Switch 1 Active
Fall below, Exceeding
Use this parameter to select the edge for activating the
switch.
-
Off - Deactivated
-
Fall below - If down-scaled
-
Exceeding - If up-scaled
Summary of Contents for SP8-10
Page 8: ...IM P707 01 CTLS Issue 1 8 SP8 10 Smart positioner Label example ...
Page 51: ...IM P707 01 CTLS Issue 1 51 SP8 10 Smart positioner Fig 28 Continued on next page ...
Page 52: ...IM P707 01 CTLS Issue 1 52 SP8 10 Smart positioner Fig 29 Continued on next page ...
Page 53: ...IM P707 01 CTLS Issue 1 53 SP8 10 Smart positioner Fig 30 ...
Page 86: ...IM P707 01 CTLS Issue 1 86 SP8 10 Smart positioner ...
Page 87: ...IM P707 01 CTLS Issue 1 87 SP8 10 Smart positioner ...
Page 88: ...IM P707 01 CTLS Issue 1 88 SP8 10 Smart positioner ...