IM-P707-01
CTLS Issue 1
36
SP8-10 Smart positioner
3.3.15 Pneumatic connections - Air supply
Instrument air*
Purity
Maximum particle size: 5 μm
Maximum particle density: 5 mg/m
3
Oil content
Maximum concentration 1 mg/m
3
Pressure dew point
10 K below operating temperature
Supply pressure**
Standard design:
1.4 to 6 bar (20 to 90 psi)
Air consumption***
< 0.03 kg/h/0.015 scfm
*
Free of oil, water and dust in accordance with DIN/ISO 8573-1. Pollution and oil content in accordance
with Class 3:3:3
**
Do not exceed the maximum output pressure of the actuator
***
Independent of supply pressure
3.3.16 Compressed air output
Range
0 to 10 bar (0 to 145 psi)
Air capacity
Standard: 40 kg/h (31 Nm
3
/h/20 scfm)
Optional: 50 kg/h (40 Nm
3
/h/23 scfm)
Output function
For single acting or double acting actuators
Air is vented from actuator or actuator is blocked in case of (electrical) power failure
Shut-off values
End position 0 % = 0 to 45 %
End position 100 % = 55 to 100 %