Series 185/285 Smart Positioners

Specifications - Installation and Operating Instructions

Bulletin V-185/285

DWYER INSTRUMENTS, INC. 

Phone: 219/879-8000

www.dwyer-inst.com

P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A. 

Fax: 219/872-9057

e-mail: [email protected]

SPECIFICATIONS
Input Signal:

4 to 20 mA DC.

Input Impedance: 

460 Ω max @ 20 mA DC.

Enclosure: 

Aluminum, SS. 

Air Supply: 

35 to 116 psi (2.4 to 9 bar).

Air Connection: 

1/4˝ NPT.

Gage Connection: 

1/8˝ NPT.

Conduit Connection: 

1/2˝ NPT.

Linearity: 

±0.5% FS.

Hysteresis: 

±0.5% FS.

Sensitivity: 

±0.2% FS.

Repeatability:

±0.3% FS.

Air Consumption: 

.0004 scfm (.01 LPM) at 20 psig (1.4 bar) supply.

Flow Capacity: 

2.1 scfm (60 LPM) at 20 psig (1.4 bar) supply.

Stroke: 

185: 0.5 to 6 in (10 to 150 mm); 285: 0 to 90°. 

Enclosure Rating: 

NEMA 4X (IP66).

Temperature:

Operating: -22 to 185°F (-30 to 85°C).

Weight: 

185: 3.3 lb (1.5 kg); 285: 6.4lb (2.9 kg).

Lever:

185: .39 to 1.57 in (10 to 40 mm); 285: NAMUR.

The Series 185 and 285 Smart Positioners

control valve movements accurately

using an input signal of 4 to 20 mA from the controller. In addition, a highly efficient
microprocessing operator built into the product performs various functions such as
auto calibration, PID control, alarm and Hart

®

protocol.

Features

• LCD allows the user to directly check the positioner condition in the field.
• Endures severe vibration.
• Operates normally regardless of changes in supply pressure during operation.
• Simple to use auto calibration.
• Easily equipped on small actuators because of its small size.
• Low air consumption reduces operating cost.
• Can be used in low voltage (8.5 V), leaving no limitation in controller.
• HART

®

communication available for configurating parameters or monitoring the 

valve position.

• Analog feedback signal (4 to 20 mA).
• The adjustment of valve characteristics (linear, quick open, equal percentage)

available.

• Tight shut-close and shut-open can be set in the programming menu.
• PID parameters can easily be adjusted in the field without additional

communicator.

• Split ranges such as 4 to 12 mA, with 12 to 20 mA available. 
• The positioner can manually actuate the valve or damper.
• An air filter regulator can be mounted directly to the positioner.

 

LCD SCREEN

SMART POSITIONER

3-27/32

[97.50]

3-1/64

[76.50]

4-7/64

[104.20]

SUPPLY
1/4 NPT

2-33/64

[64.00]

2-11/32

[59.60]

4-13/32

[111.90]

STAINLESS STEEL

4-31/64

[113.8]

STANDARD

CONDUIT ENTRY

1/2 NPT

8-31/64

[215.70]

DOUBLE

ACTION

SINGLE
ACTION

3-47/64

[95.00]

Series 185

Series 285

HART

® 

is a registered trademark of Hart Communication Foundation

Summary of Contents for PROXIMITY 185 Series

Page 1: ...uto calibration PID control alarm and Hart protocol Features LCD allows the user to directly check the positioner condition in the field Endures severe vibration Operates normally regardless of change...

Page 2: ...5 Four M8 plate washers Installing Series 185 with Bracket It is necessary to make a proper bracket to attach on the actuator yoke The most important considerations in the design of the bracket are as...

Page 3: ...gulator on the actuator When the stroke is both 0 and 100 the feedback lever should not reach to the lever stopper on the backside of the Series 185 unit If the feedback lever reaches the lever stoppe...

Page 4: ...o NAMUR shaft 5 Once the fork lever position is set lock the check nuts on the bottom of the fork lever by turning clockwise Set the upper height of the fork lever to 24 to 43 6 to 11 mm lower than th...

Page 5: ...afety of the positioner and system 2 The ground terminals are inside the terminal in the center of the terminal plate and outside terminal beside outer cable entry Use any ground terminal that is avai...

Page 6: ...2 mode Auto 2 calibration is started and the next modes are displayed in order on the LCD Normally it will take 3 to 5 minutes for auto calibration in AUTO2 mode Duration may vary based on actuators v...

Page 7: ...just PT value with UP or DOWN Adjusted value is applied immediately without additional operation Users can easily check its adjustment by changing the current input signal to the positioner Optimum co...

Page 8: ...displayed 4 Push ESC to exit CHAR LIN mode User Characteristics USER SET When a specific characteristic is needed but not included in the above characteristics the user can make a specific characteris...

Page 9: ...ollows Error Code This code is displayed when the Series 185 and 285 positioner control becomes impossible Code C D applies YT 2500L VERSION HART V POL AddR bIAS VI 0Y 0d FULL_OP FULL_CL VM NOR Erro V...

Page 10: ...The angle of feedback lever is too small Time elapsed for either full open or full close is less than 1 second The size of the actuator is too small Pv zero is below 100 The angle of feedback lever i...

Reviews: