background image

Parameter Mode (PARAM)
Parameter Types

There are four parameter modes: Dead Zone, KP, KI, and KD.
These values are reflected as soon as they are changed, therefore the appropriate
values are found by checking the valve’s motion in real time. 

Adjustment of Dead Zone (dEAdZONE)

This is the range of error % that the positioner is not adjusted. Hunting or oscillation
due to friction between the stem and packing is prevented by this parameter.
1. Press and hold <ENTER> at RUN mode for 6 seconds and AUTO CAL 

message appears.

2. Scroll with <DOWN> until PARAM mode is displayed.
3. Push <ENTER> and dEAdZONE mode is displayed.
4. Push <ENTER> again and *EAdZONE message appears.
5. Adjust dEAdZONE value by pushing <UP> or <DOWN>. Adjusted valued is 

applied immediately without additional operation. Users can easily check its 
adjustment by changing the current input signal to the positioner. Optimum 
control value is found by adjusting values during the valve operation.

6. Push <ENTER> to save the value. +EAdZONE message appears on LCD.
7. Push <ESC> to exit dEAdZONE mode. 

KP

1. Press and hold <ENTER> at RUN mode for 6 seconds and AUTO CAL 

message appears.

2. Scroll with <DOWN> until PARAM mode is displayed.
3. Push <ENTER> and dEAdZONE mode is displayed.
4. Scroll with <DOWN> until KP mode is displayed.
5. Push <ENTER> at KP mode and *KP message appears on LCD.
6. Adjust KP value with <UP> or <DOWN>. Adjusted value is applied immediately 

without additional operation. Users can easily check its adjustment by changing 
the current input signal to the positioner. Optimum control value is found by 
adjusting the values during valve operation.

7. Push <ENTER> to save the value and +KP message appears on LCD.
8. Push <ESC> to exit KP mode.

PT 

1. Press and hold <ENTER> at RUN mode for 6 seconds and AUTO CAL 

message appears.

2. Scroll with <DOWN> until PARAM mode is displayed.
3. Push <ENTER> and dEAdZONE mode is displayed.
4. Scroll with <DOWN> until PT mode is displayed.
5. Push <ENTER> at PT mode and *PT message appears on LCD.
6. Adjust PT value with <UP> or <DOWN>. Adjusted value is applied immediately 

without additional operation. Users can easily check its adjustment by changing 
the current input signal to the positioner. Optimum control value is found by 
adjusting the values during valve operation.

7. Push <ENTER> to save the value and +PT message appears on LCD.
8. Push <ESC> to exit KP mode.

HAND CAL

When  auto  calibration  is  started,  Series  185  and  285  positioners  set  zero  points
and end points based on full stroke. HAND CAL allows for user defined zero and
end points.

Hand Calibration Types

PV_ZERO: Edit mode to change the zero point of valve.
PV_END: Edit mode to change the end point of a valve.
TR_ZERO: Edit mode to change the zero point of transmitter.
TR_END: Edit mode to change the end point of transmitter. 

Adjustment of valve zero point (1 to 5) and end point (6 to 10).

PV_ZERO

1. Press and hold <ENTER> at RUN mode for 6 seconds and AUTO CAL 

message appears.

2. Scroll with <DOWN> until HAND CAL mode is displayed.
3. Push <ENTER> and PV_ZERO mode is displayed.
4. Push <ENTER> at PV_ZERO mode and *PZ mode is started. The valve stem 

will move automatically to the current zero point. On the LCD, the valve stroke 
is displayed as 0%. *PZ indicates the zero point is ready to be set.

5. Adjust valve stem by pushing <UP> or <DOWN>. When valve stem is at the 

desired zero point, save it by pushing <ENTER>.

6. Push <ESC> to exit PV_ZERO mode.

PV_END

1. To change valve end point, scroll with <DOWN> at HAND CAL menu and select
PV_END.
2. Push <ENTER> at PV_END mode and *PE mode is displayed. The valve stem 

will move automatically to the current end point. On the LCD, the valve stroke 
is displayed as 100%. *PE indicates the end point is ready to be set.

3. Adjust valve stem by pushing <UP> or <DOWN>. When the valve stem is at 

the desired end point, save it by pushing <ENTER>.

4. Push <ESC> to exit PV_END mode.

<ENTER>

6 seconds

<ENTER>

6 seconds

<ENTER>

<ENTER>

<UP>/<DOWN>

then <ENTER>

<ESC>

3 times

COMPLETED

<ENTER>

<DOWN>

3 times

<ENTER>

<UP>/<DOWN>

then <ENTER>

<ESC>

3 times

COMPLETED

<ENTER>

<DOWN>

7 times

<ENTER>

<UP>/<DOWN>

then <ENTER>

<ESC>

3 times

COMPLETED

<ENTER>

6 seconds

<DOWN>

3 times

<ENTER>

<ENTER>

<UP>/<DOWN>

then <ENTER>

<ESC>

<DOWN>

<ENTER>

<UP>/<DOWN>

then <ENTER>

<ESC>

COMPLETED

Summary of Contents for PROXIMITY 185 Series

Page 1: ...uto calibration PID control alarm and Hart protocol Features LCD allows the user to directly check the positioner condition in the field Endures severe vibration Operates normally regardless of change...

Page 2: ...5 Four M8 plate washers Installing Series 185 with Bracket It is necessary to make a proper bracket to attach on the actuator yoke The most important considerations in the design of the bracket are as...

Page 3: ...gulator on the actuator When the stroke is both 0 and 100 the feedback lever should not reach to the lever stopper on the backside of the Series 185 unit If the feedback lever reaches the lever stoppe...

Page 4: ...o NAMUR shaft 5 Once the fork lever position is set lock the check nuts on the bottom of the fork lever by turning clockwise Set the upper height of the fork lever to 24 to 43 6 to 11 mm lower than th...

Page 5: ...afety of the positioner and system 2 The ground terminals are inside the terminal in the center of the terminal plate and outside terminal beside outer cable entry Use any ground terminal that is avai...

Page 6: ...2 mode Auto 2 calibration is started and the next modes are displayed in order on the LCD Normally it will take 3 to 5 minutes for auto calibration in AUTO2 mode Duration may vary based on actuators v...

Page 7: ...just PT value with UP or DOWN Adjusted value is applied immediately without additional operation Users can easily check its adjustment by changing the current input signal to the positioner Optimum co...

Page 8: ...displayed 4 Push ESC to exit CHAR LIN mode User Characteristics USER SET When a specific characteristic is needed but not included in the above characteristics the user can make a specific characteris...

Page 9: ...ollows Error Code This code is displayed when the Series 185 and 285 positioner control becomes impossible Code C D applies YT 2500L VERSION HART V POL AddR bIAS VI 0Y 0d FULL_OP FULL_CL VM NOR Erro V...

Page 10: ...The angle of feedback lever is too small Time elapsed for either full open or full close is less than 1 second The size of the actuator is too small Pv zero is below 100 The angle of feedback lever i...