Valve Mode

This mode adjusts the various characteristics. 

Action Type (ACT)

It can be set to Direct Action (DA) or Reverse Action (RA).

Adjustment of Acting Type (ACT)

1. Press and hold <ENTER> at RUN mode for 6 seconds and AUTO CAL 

message appears.

2. Scroll with <DOWN> until VALVE mode is displayed.
3. Push <ENTER> and ACT RA (in case of Reverse Acting) is displayed.
4. Push <ENTER> and *ACT RA is displayed.
5. Adjust to *ACT DA by pushing <UP> or <DOWN> and save it with <ENTER>. 

+ACT DA message appears.

6. Push <ESC> to exit ACT RA mode.

Characteristics (CHAR)

Set  Characteristics.  There  are  three  types  of  valve  characteristics:  Linear  (LIN),
EQ%  (EQ),  and  Quick  Open  (QO).  The  following  is  the  example  of  the  three
characteristic curves.  

Adjustment of Characteristics (CHAR)

1. To change linear characteristics, scroll with <DOWN> at VALVE menu and select
CHAR LIN (in case of linear characteristics).
2. Push <ENTER>. *HAR LIN mode is displayed and charactertistics can be set to
LIN, EQ, QO or USR.
3. Adjust characteristics (ex: EQ) by pushing <UP> or <DOWN> and save it with
<ENTER>. + HAR EQ is displayed.
4. Push <ESC> to exit CHAR LIN mode. 

User Characteristics (USER SET)

When  a  specific  characteristic  is  needed  but  not  included  in  the  above
characteristics, the user can make a specific characteristic curve by choosing 16
points voluntarily.

Adjustment of User Characteristics (USER SET)

1. Push <ENTER> at VALVE mode and scroll with <DOWN> to select USER SET.
2. Push <ENTER>. *PO SET mode is displayed. In this mode, users can adjust the
first point of characteristic in 16 points. the number on the LCD is the valve stroke
percentage set to P0.
3. Adjust the valve stroke percentage using <UP> or <DOWN>.
4. Save  with  <ENTER>.  While  P0  value  is  being  saved,  *P1  SET  mode  is
displayed.
5. *P1  SET mode  is  used  to  adjust  the  second  point  characteristic  in  16  points.
Adjustment method is the same as P0* SET mode.
6. Continue steps from P2 to P15.
7. After adjusting valve stroke percentage at *P15 SET mode, save with <ENTER>.
8. +SER SET is displayed. All sixteen points of valve stroke percentage are set.
9. Push <ESC> to exit USER SET mode. 

100%

Strok

0

4

20

mA

Quick Open

Linear

EQ%

<ENTER>

6 seconds

<DOWN>

3 times

<ENTER>

<ENTER>

<UP>/<DOWN>

then <ENTER>

<ESC>

3 times

COMPLETED

<ENTER>

6 seconds

<DOWN>

3 times

<ENTER>

<UP>/<DOWN>

then <ENTER>

<ENTER>

<UP>/<DOWN>

then <ENTER>

<ENTER>

<ENTER>

6 seconds

Summary of Contents for PROXIMITY 185 Series

Page 1: ...uto calibration PID control alarm and Hart protocol Features LCD allows the user to directly check the positioner condition in the field Endures severe vibration Operates normally regardless of change...

Page 2: ...5 Four M8 plate washers Installing Series 185 with Bracket It is necessary to make a proper bracket to attach on the actuator yoke The most important considerations in the design of the bracket are as...

Page 3: ...gulator on the actuator When the stroke is both 0 and 100 the feedback lever should not reach to the lever stopper on the backside of the Series 185 unit If the feedback lever reaches the lever stoppe...

Page 4: ...o NAMUR shaft 5 Once the fork lever position is set lock the check nuts on the bottom of the fork lever by turning clockwise Set the upper height of the fork lever to 24 to 43 6 to 11 mm lower than th...

Page 5: ...afety of the positioner and system 2 The ground terminals are inside the terminal in the center of the terminal plate and outside terminal beside outer cable entry Use any ground terminal that is avai...

Page 6: ...2 mode Auto 2 calibration is started and the next modes are displayed in order on the LCD Normally it will take 3 to 5 minutes for auto calibration in AUTO2 mode Duration may vary based on actuators v...

Page 7: ...just PT value with UP or DOWN Adjusted value is applied immediately without additional operation Users can easily check its adjustment by changing the current input signal to the positioner Optimum co...

Page 8: ...displayed 4 Push ESC to exit CHAR LIN mode User Characteristics USER SET When a specific characteristic is needed but not included in the above characteristics the user can make a specific characteris...

Page 9: ...ollows Error Code This code is displayed when the Series 185 and 285 positioner control becomes impossible Code C D applies YT 2500L VERSION HART V POL AddR bIAS VI 0Y 0d FULL_OP FULL_CL VM NOR Erro V...

Page 10: ...The angle of feedback lever is too small Time elapsed for either full open or full close is less than 1 second The size of the actuator is too small Pv zero is below 100 The angle of feedback lever i...

Reviews: