6. Insert the connection bar attached on the actuator clamp into the slot of Series
185’s feedback lever. In order to reduce hysteresis, it should appear as shown:

7. Check that the Series 185’s feedback lever is level at 50% of valve stroke. If not,
move  bracket  or  feedback  link  until  it  is  level.  Product  linearity  becomes  work  if
Series 185 is installed without being level at 50% of valve stroke.

8. Check valve stroke. The numbers indicating stroke are carved in the Series 185’s
feedback  lever.  Set  the  connection  bar  attached  on  the  actuator  clamp  to  the
number on the feedback lever applicable to valve stroke as shown in the following
picture. To set the connection bar and the number, move the bracket attached on
Series 185 or connection bar from side to side. 

NOTE: After installation, operate the valve from 0 to 100% stroke using an air filter
regulator on the actuator. When the stroke is both 0 and 100%, the feedback lever
should not reach to the lever stopper on the backside of the Series 185 unit. If the
feedback  lever  reaches  the  lever  stopper,  move  attachment  of  Series  185  away
from the yoke center. 

9. Once the Series 185 is installed according to the above procedures, tighten the
bolts and nuts of the bracket and feedback lever connection bar completely. 

Series 285 Installation

Series  285  is  designed  for  rotary  motion  valves  such  as  Dwyer  Instruments’  ball
and butterfly valves using rack and pinion, scotch yoke or complex type actuators
whose  stem  is  rotated  90°.  Series  285  positioners  consist  of  the  following
components:
Series 285 main body
Fork lever and lever spring to attach on actuator 
1 bracket
Four hex bolts M8x1.25P
Four M8 plate washers

Series 285 Installation Example of Fork Lever

60

50

40

90

°

50%

LCD SCREEN

SMART POSITIONER

30

10

20

40

50

60

70

150

140

130

120

110

100

90

80

40

20

10

30

80

90

100

110 120 130

140 150

70

60

50

No

 To

uc

h !

Stroke 40 mm

Stroke 90 mm

Summary of Contents for PROXIMITY 185 Series

Page 1: ...uto calibration PID control alarm and Hart protocol Features LCD allows the user to directly check the positioner condition in the field Endures severe vibration Operates normally regardless of change...

Page 2: ...5 Four M8 plate washers Installing Series 185 with Bracket It is necessary to make a proper bracket to attach on the actuator yoke The most important considerations in the design of the bracket are as...

Page 3: ...gulator on the actuator When the stroke is both 0 and 100 the feedback lever should not reach to the lever stopper on the backside of the Series 185 unit If the feedback lever reaches the lever stoppe...

Page 4: ...o NAMUR shaft 5 Once the fork lever position is set lock the check nuts on the bottom of the fork lever by turning clockwise Set the upper height of the fork lever to 24 to 43 6 to 11 mm lower than th...

Page 5: ...afety of the positioner and system 2 The ground terminals are inside the terminal in the center of the terminal plate and outside terminal beside outer cable entry Use any ground terminal that is avai...

Page 6: ...2 mode Auto 2 calibration is started and the next modes are displayed in order on the LCD Normally it will take 3 to 5 minutes for auto calibration in AUTO2 mode Duration may vary based on actuators v...

Page 7: ...just PT value with UP or DOWN Adjusted value is applied immediately without additional operation Users can easily check its adjustment by changing the current input signal to the positioner Optimum co...

Page 8: ...displayed 4 Push ESC to exit CHAR LIN mode User Characteristics USER SET When a specific characteristic is needed but not included in the above characteristics the user can make a specific characteris...

Page 9: ...ollows Error Code This code is displayed when the Series 185 and 285 positioner control becomes impossible Code C D applies YT 2500L VERSION HART V POL AddR bIAS VI 0Y 0d FULL_OP FULL_CL VM NOR Erro V...

Page 10: ...The angle of feedback lever is too small Time elapsed for either full open or full close is less than 1 second The size of the actuator is too small Pv zero is below 100 The angle of feedback lever i...