Structure

The structure of the 185 is shown below. The Series 285 structure is the same as
the linear model without the feedback lever. 

Installation

Note: When the positioner is replaced or installed with the actuator, make sure of
the following:
-All inputs and supply pressure to the valve, actuator and other instruments must
be shut down.
-The control valve must be separated from the system with a bypass valve or other
equipment so that the entire system does not shut down.
-No pressure remains in the actuator.

Tools For Installation

• Hexagonal wrenches
• (+) Screw driver
• (-) Screw driver
• Spanners for hexagon head bolts

Series 185 Installation

Series  185  is  used  for  linear  motion  valves  such  as  Dwyer  Instruments’  globe
valves using a spring return type diaphragm actuator or piston actuator. The Series
185  consists  of  the  following  components.  Be  sure  that  all  the  components  are
included. 

1. Series 185 main body
2. Feedback lever and lever spring
3. Flange nut (attached on the bottom of main shaft of Series 185 body)
4. Four hexagon head bolts M8x1.25P
5. Four M8 plate washers

Installing Series 185 with Bracket

It is necessary to make a proper bracket to attach on the actuator yoke. 
The most important considerations in the design of the bracket are as follows:
- Series 185 feedback lever should be at 50% of valve stroke.
-  Feedback  level  connection  bar  of  actuator  clamp  should  be  connected  in  the
position  so  that  the  valve  stroke  and  the  numbers  carved  on  feedback  lever  are
fitted. If the bracket meets the above conditions, Series 185 can be installed very
easily. 

2. Assemble Series 185 and bracket with bolts. Use standard bolts in bolt holes on
the backside of the unit.

Installing Series 185 with Bracket

3. After assembling Series 185 and bracket with bolts, attach it using bolt holes of
actuator yoke. Do not tighten completely, there must be some space. 

4.  Install  bar  connected  with  Series  185’s  feedback  lever  on  the  actuator  clamp.
The  slot  length  between  Series  185’s  feedback  lever  is  .26˝  (6.5  mm),  so  the
diameter of the connection bar should be less than .25˝ (6.3 mm). 

5. Connect the air filter regulator with the actuator temporarily. Set supply pressure
of air filter so that the actuator clamp is positioned at 50% of valve stroke. 

LCD SCREEN

SMART POSITIONER

0

100

50

LCD SCREEN

SMART POSITIONER

Summary of Contents for PROXIMITY 185 Series

Page 1: ...uto calibration PID control alarm and Hart protocol Features LCD allows the user to directly check the positioner condition in the field Endures severe vibration Operates normally regardless of change...

Page 2: ...5 Four M8 plate washers Installing Series 185 with Bracket It is necessary to make a proper bracket to attach on the actuator yoke The most important considerations in the design of the bracket are as...

Page 3: ...gulator on the actuator When the stroke is both 0 and 100 the feedback lever should not reach to the lever stopper on the backside of the Series 185 unit If the feedback lever reaches the lever stoppe...

Page 4: ...o NAMUR shaft 5 Once the fork lever position is set lock the check nuts on the bottom of the fork lever by turning clockwise Set the upper height of the fork lever to 24 to 43 6 to 11 mm lower than th...

Page 5: ...afety of the positioner and system 2 The ground terminals are inside the terminal in the center of the terminal plate and outside terminal beside outer cable entry Use any ground terminal that is avai...

Page 6: ...2 mode Auto 2 calibration is started and the next modes are displayed in order on the LCD Normally it will take 3 to 5 minutes for auto calibration in AUTO2 mode Duration may vary based on actuators v...

Page 7: ...just PT value with UP or DOWN Adjusted value is applied immediately without additional operation Users can easily check its adjustment by changing the current input signal to the positioner Optimum co...

Page 8: ...displayed 4 Push ESC to exit CHAR LIN mode User Characteristics USER SET When a specific characteristic is needed but not included in the above characteristics the user can make a specific characteris...

Page 9: ...ollows Error Code This code is displayed when the Series 185 and 285 positioner control becomes impossible Code C D applies YT 2500L VERSION HART V POL AddR bIAS VI 0Y 0d FULL_OP FULL_CL VM NOR Erro V...

Page 10: ...The angle of feedback lever is too small Time elapsed for either full open or full close is less than 1 second The size of the actuator is too small Pv zero is below 100 The angle of feedback lever i...