Manual for clima BSK4-F / clima BSK4-F230
LON fire damper actuator 4 ports
Order No.: 421 404 / 421 405
Configuration parameters
UCPTfireSD
ActuatorType
Type of damper - end
positions and control
Type:
Enumeration
Range of values:
firesmokedampers_t
0
FSDA_NO_
CTRL_1SW
no control,
1 safety trigger
sensor
1
FSDA_NO_
CTRL_2SW
no control, 2 end-
position switches
2
FSDA_CTRL_2SW
control, 2 end-
position switches
-1
FSDA_NUL
invalid / not used
Presetting:
not used {-1)
UCPTswitchMap
Assignment of the end-
position switches or the
safety trigger sensor
Type:
Structure
Structure:
.switch1 channel of
normal position if
the damper has
2end-position
switches or
channel of safety
trigger sensor
.switch2 channel of safety
pos. if the
damper has 2
end-position
switches
Range of values:
for both elements :
0
No channel
assigned
1-8
Channel number
Presetting:
no channel assigned (0, 0)
SCPTdirection
Type of damper - safety
position
Type:
SNVT_state
Range of values:
only second bit is
relevant:
0
closed (fire
damper)
1
opend (smoke
damper)
Presetting:
closed
(0000000000000000)
SCPToffDely
Spring return time
Type:
SNVT_elapsed_tm
Range of values:
.minute
0-60 Minutes
.second
0-60 Seconds
.day / .hour / .millisecond
always 0
Presetting:
20 Seconds (0,0,0,20,0)
SCPTdriveTime
Damper drive duration
Type:
SNVT_time_sec
Range of values: 0 ...6553,4 Seconds
Presetting:
50 Seconds (500)
SCPTzoneNum
Fire protection zone
number or localization
Type:
unsigned long
Range of values:
0 ...65535 zone number
Presetting:
65535
Version 3.01
Page 25 / 39
01.09.2020