![spega 421 404 Technical Manual Download Page 21](http://html1.mh-extra.com/html/spega/421-404/421-404_technical-manual_1346187021.webp)
Manual for clima BSK4-F / clima BSK4-F230
LON fire damper actuator 4 ports
Order No.: 421 404 / 421 405
the network variable nvoStatus. The following commands are to be used for
the status request:
nviRequest
Meaning
{RQ_UPDATE_STATUS, 0} determining the status of the device
{RQ_UPDATE_STATUS, i}
determining the status of the i-th function object
on the device (first object after the NodeObject
has the number 1)
Status screen
Send a telegram to the network variable nviRequest to query all supported
status messages of the device or a specific object.
nviRequest
Meaning
{RQ_REPORT_MASK, 0}
determining the status of the device
{RQ_REPORT_MASK, i}
determining the status of the i-th function object
on the device (first object after the NodeObject
has the number 1)
In the status screen, all status elements that can be occupied by the
corresponding function object or device are set.
Version 3.01
Page 21 / 39
01.09.2020