Manual for clima BSK4-F / clima BSK4-F230
LON fire damper actuator 4 ports
Order No.: 421 404 / 421 405
nvoUpSwitch
state output of first
end-position switch
(normal position)
Type:
SNVT_switch
Range of values:
(0,0)
open
(1,100) closed
Presetting:
(0,0)
nvoDownSwitch
state output of second
end-position switch
(safety position)
Type:
SNVT_switch
Range of values:
see nvoUpSwitch
Presetting:
(0,0)
nvoDriveStatus
status output
Type:
SNVT_state
Structure:
Bitfield elements :
.bit4
mechanical_fault
reasons: no
drive after drive
command or
drive end not
reached
.bit6
over_range time
overrun on drive
to safety position
.bit7
under_range
time overrun on
drive to normal
position
.bit10 comm_failure
response
timeout at
nviDriveValue or
at nviGroupValue
of assigned
Group
.bit11 fail_self_test
maintenance not
successful
.bit12 self_test_in
_progress
maintenance
active
.bit15 in_alarm
fire alert (see
nvoFire)
Presetting:
{0:0:0:0:0:0:0:0:
0:0:0:0:0:0:0:0}
Transmission:
on change
nvoDrivePos
Actual actuator position
detected via end -position
switches
Type:
SNVT_hvac_emerg
Range of values:
emerg_t:
0
EMERG_NORMAL
normal position
5
EMERG_FIRE
safety position
-1
EMERG_NUL
driving, not at
one of the
end positions
additional value:
-4
EMERG_UNDEF
both end-position
switches closed
Presetting:
EMERG_NORMAL(0)
Transmission:
adjustable via
SCPTmaxSendTime
Version 3.01