![spega 421 404 Technical Manual Download Page 18](http://html1.mh-extra.com/html/spega/421-404/421-404_technical-manual_1346187018.webp)
Manual for clima BSK4-F / clima BSK4-F230
LON fire damper actuator 4 ports
Order No.: 421 404 / 421 405
3.2.2 SC421404EC_02 Software objects
Count
Object
Interface
1
NodeObject
version 4.1
4
FireSmokeDamper
Actuator
version 2.1
2
FireCompartement
Group
version 0.1
Version 3.01
Page 18 / 39
01.09.2020
NodeObject_04
UFPTnodeObject #0
nvoStatus
(SNVT_obj_status)
nviRequest
(SNVT_obj_request)
nvoFileDirectory
(SNVT_adress)
FireSmokeDamperActuator_02
SFPTfireSmokeDamperActuator #11001_10
nvoDrivePos
(SNVT_hvac_emerg)
nviDriveValue
(SNVT_hvac_emerg)
nviDuctPos
(SNVT_hvac_emerg)
nvoDuctPos
(SNVT_hvac_emerg)
nvoUpSwitch
(SNVT_switch)
nvoDownSwitch
(SNVT_switch)
nvoFire
(SNVT_switch)
nvoDriveStatus
(SNVT_state)
FireCompartementGroup_00
UFPTfireCompartementGroup #23501
nviGroupValue
(SNVT_hvac_emerg)