![spega 421 404 Technical Manual Download Page 15](http://html1.mh-extra.com/html/spega/421-404/421-404_technical-manual_1346187015.webp)
Manual for clima BSK4-F / clima BSK4-F230
LON fire damper actuator 4 ports
Order No.: 421 404 / 421 405
2.6. Operation
The operating elements described below are available for commissioning and
maintenance of the fire dampers actuator modules.
Service button
The service button is used to send the neuron ID of the actuator module.
Service LED
The service LED indicates the status of the device.
LED
indicator
Remark
LED is on
Device without application
LED flashes
Device is unconfigured
LED is off
Device with application and configured
Relais button
The relay buttons S1 to S4 are used to test the damper function. Dampers
which are already in normal position cannot be tested via the relay buttons.
Status
Remark
pressed
Relay activated, damper moves to normal position
not pressed
Relay deactivated, damper moves to safety position
Version 3.01
Page 15 / 39
01.09.2020