![spega 421 404 Technical Manual Download Page 14](http://html1.mh-extra.com/html/spega/421-404/421-404_technical-manual_1346187014.webp)
Manual for clima BSK4-F / clima BSK4-F230
LON fire damper actuator 4 ports
Order No.: 421 404 / 421 405
2.5. Revisions
The devices clima BSK4-F and clima BSK4-F230 are currently available in
Revision 2. In the course of the product update, the neuron firmware of the
e.control device has been renewed.
Since the new revision requires a changed device application, we distribute
both software versions. You can determine which device revision your
e.control device has by looking at the neuron ID sticker on the case:
Revision
Application
Information
Rev 1
SC421404EC_02
Rev 2
SC421404EC_12
XIF upgrade from SC421404EC_02 possible
For revision 2 the following application note must also be observed:
The present product uses a processor of a newer generation for which the
application download is only supported from LNS version 4.02. For this
reason, with lower LNS versions you also need the Spega Update Tool, which
you can download from the download area on our homepage
.
We recommend the following procedure for LNS versions lower than 4.02:
1) With the current setup, a new device template for the current device
appears in the system plug-in "Device template manager". Add this to
your network.
2) Create the required devices offline in your database (without
commissioning them) and note down the corresponding neuron ID's.
3) Then close your database and start the Spega Update Tool. Make sure
that there are no routers between the LON interface of your PC and
the devices, use a local interface if necessary.
4) Now load the desired application into your devices with the Spega
Update Tool.
5) You can then reopen your database and commission the devices
without explicitly loading the application.
Version 3.01
Page 14 / 39
01.09.2020