3.3. Description of software objects
The individual functional objects are described in greater detail below.
3.3.1 NodeObject
Interface description
Network interface
Version
4.01
Status
01.01.2008
NodeObject_04
UFPT_NodeObject #0
nvoStatus
(SNVT_obj_status)
nviRequest
(SNVT_obj_request)
nvoFileDirectory
(SNVT_adress)
SCPTdevMajVer
(SCPT #165 unsigned short)
SCPTdevMinVer
(SCPT #166 unsigned short)
SCPTlocation
(SCPT #17
SNVT_str_asc)
Network variables
nviRequest
Default network input
for receiving
management
commands
Type:
SNVT_obj_request
Presetting:
{0, RQ_NORMAL}
nvoStatus
Output of status data for
received request
management commands
via nviRequest
Type:
SNVT_obj_status
Transmission:
On request via nviRequest
nvoFile
Directory
Provides the start
address of the config
file directory of the
device
Type:
SNVT_address
Transmission:
During file transfer or
polling
Version 3.01