Manual for clima BSK4-F / clima BSK4-F230
LON fire damper actuator 4 ports
Order No.: 421 404 / 421 405
Configuration parameters
SCPTdevMajVer
Major version of
application
Type:
SCPT #165 (read only)
unsigned short
Value:
Application specific
SCPTdevMinVer
Minor version of
application
Type:
SCPT #166 (read only)
unsigned short
Value:
Application specific
SCPTlocation
Extended description
of the device location
Type:
SCPT #17 SNVT_str_asc
Presetting:
{ 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 }
Function description
The NodeObject is used to manage all function objects of the device. It
enables status requests and provides error messages for the device and its
objects.
Device management
Various requests and commands can be sent to the device and its function
objects via the network variable nviRequest. The availability of the commands
for the individual function objects can be found in the respective object
description. In the individual applications, additional requests are supported
in some cases.
nviRequest.
object_request
Command
Meaning
RQ_NORMAL
Normal function resets function objects that are in
'override' or 'disabled' status
RQ_UPDATE_STATUS Status request
determining the status of the
device or a function object
RQ_REPORT_MASK
Status screen
returns all states that can be taken
by the device or function object
Status request
The status of the device and individual objects can be requested via the
network variable nviRequest. The response to the request can be taken from
Version 3.01