Manual for clima BSK4-F / clima BSK4-F230LON fire damper actuator 4 portsOrder No.: 421 404 / 421 405
Technical Manual clima BSK4-F/
F230
Version 3.01
Radevormwald, 01.09.2020
Page 1 / 39
01.09.2020
Page 1: ...nual for clima BSK4 F clima BSK4 F230 LON fire damper actuator 4 ports Order No 421 404 421 405 Technical Manual clima BSK4 F F230 Version 3 01 Radevormwald 01 09 2020 Version 3 01 Page 1 39 01 09 202...
Page 2: ...cription 6 2 1 Technical Data 7 2 2 Mounting 11 2 3 Installation 12 2 4 Commissioning 13 2 5 Revisions 14 2 6 Operation 15 2 7 Treatment of disorders 16 3 Applications 17 3 1 Available applications 17...
Page 3: ...of the system Please store this manual in a location which is easily accessible to all users 1 1 Using the manual The manual is aimed at all persons concerned with the planning installation commission...
Page 4: ...itions spega reserves the right to refuse liability for damage to the product Additionally spega shall not be liable for consequential damage and or injury to people or property in such cases 1 4 Expl...
Page 5: ...tion of the device is determined by the application software Only software which has been approved by spega should be used for this device The system integrator should ensure that the software and rel...
Page 6: ...control switches Both modules support a monitoring of 8 potential free end position switches LED indicators provide a status information about the actual status of the end position switches and there...
Page 7: ...s motor supply is identical to module power supply Terminals Power supply 1 x 2 pole and 1 x 6 pole clamp terminal for solid or flexible wires 0 1 2 5 mm Network 1 x 4 pole clamp terminal for solid or...
Page 8: ...x W x D Type location of installation Assembly on ventilation ducts in hollow floors suspended ceilings Ambient conditions Operating temperature 5 C 45 C Storage temperature 25 C 55 C Transport tempe...
Page 9: ...ole clamp terminal 6xL 2xPE 6xN for solid or flexible wires 0 1 2 5 mm Network 1 x 4 pole clamp terminal for solid or flexible wires 0 1 2 5 mm Binary inputs 2 x 8 pole clamp terminal for 8 inputs eac...
Page 10: ...oors suspended ceilings Ambient conditions Operating temperature 5 C 45 C Storage temperature 25 C 55 C Transport temperature 25 C 70 C Relative humidity 5 93 without condensation Installation height...
Page 11: ...f the respective country must be observed when planning and installing electrical systems The device specifications must be observed The installation of the input module is in hollow floors suspended...
Page 12: ...transceiver to connect to a free topology LON network The module is supplied by 24V AC or DC The module power supply is identical to the motor supply Please use the following connection diagram BSK 1...
Page 13: ...E1 2 E2 1 E2 2 A B A B E3 1 E3 2 E4 1 E4 2 M4 M4 M3 M3 M2 M1 M2 M1 230V 230V AC L N PE PEPEPEPEPEPE If dampers with two end position switches are used connect them to two adjacent binary inputs For t...
Page 14: ...pplication download is only supported from LNS version 4 02 For this reason with lower LNS versions you also need the Spega Update Tool which you can download from the download area on our homepage ww...
Page 15: ...e LED The service LED indicates the status of the device LED indicator Remark LED is on Device without application LED flashes Device is unconfigured LED is off Device with application and configured...
Page 16: ...ark LED is on Contact is not closed LED is off Contact is closed 2 7 Treatment of disorders Disorder Treatment service LED off Check whether the power supply is ensured service LED lights up constantl...
Page 17: ...ith LNS based system integration tools the use of the specified resource files is recommended 3 1 Available applications SC421404EC_02 Monitoring of up to 8 end position switches and control of up to...
Page 18: ...01 09 2020 NodeObject_04 UFPTnodeObject 0 nvoStatus SNVT_obj_status nviRequest SNVT_obj_request nvoFileDirectory SNVT_adress FireSmokeDamperActuator_02 SFPTfireSmokeDamperActuator 11001_10 nvoDrivePos...
Page 19: ...ctory SNVT_adress SCPTdevMajVer SCPT 165 unsigned short SCPTdevMinVer SCPT 166 unsigned short SCPTlocation SCPT 17 SNVT_str_asc Network variables nviRequest Default network input for receiving managem...
Page 20: ...its objects Device management Various requests and commands can be sent to the device and its function objects via the network variable nviRequest The availability of the commands for the individual f...
Page 21: ...first object after the NodeObject has the number 1 Status screen Send a telegram to the network variable nviRequest to query all supported status messages of the device or a specific object nviReques...
Page 22: ...tored Interface description Network interface Version 02 02 Status 16 09 2016 Version 3 01 Page 22 39 01 09 2020 SFPTfireSmokeDamperActuator SFPT 11001_10 Version_02 nvoDrivePos SNVT_hvac_emerg nviDri...
Page 23: ...EMERG_ MAINTENANCE start maintenance 7 EMERG_CLEAR _STATUS clear status Presetting EMERG_NORMAL 0 Heartbeat control adjustable via SCPTmaxRcvTime Output variables nvoFire fire state output returns fir...
Page 24: ...e to safety position bit7 under_range time overrun on drive to normal position bit10 comm_failure response timeout at nviDriveValue or at nviGroupValue of assigned Group bit11 fail_self_test maintenan...
Page 25: ...el of safety trigger sensor switch2 channel of safety pos if the damper has 2 end position switches Range of values for both elements 0 No channel assigned 1 8 Channel number Presetting no channel ass...
Page 26: ...no periodic re sent Presetting no periodic re sent 0 UCPTdrvBreak Mode Interruption mode for active maintenance Type Enumeration Range of values 1 DBM_NUL no interrupts 0 DBM_ON_FIRE maintenens ends a...
Page 27: ...parameter UCPTfireSDActuatorType For damper types without control the relay assigned to the damper object is switched off Number of end position switches There are both dampers which are limited to a...
Page 28: ...rameter SCPTdirection can be used to specify whether the end position switches are normally closed or normally open Type Endlagenschalter UCPTswitchMap Value in SCPTdirection normally closed switch 1...
Page 29: ...triggered by a run command the running times are checked as described in the next section Runtime monitoring This functionality is only available for the damper type with 2 limit switches and motoris...
Page 30: ...od it has to be updated by the application at the latest The preset value 0 deactivates the cyclical update the value is only sent when the position changes Monitoring of fire protection ducts To moni...
Page 31: ...ers x 0 Using the group objects individual fire dampers can also be assigned to a fire compartment and maintained via the corresponding group Maintenance procedure FIRE NORMAL SCPToffDely 0 5 SCPToffD...
Page 32: ...ehavior Depending on which functions are to be implemented with the fire damper objects a distinction can be made between different types of maintenance interruption In the parameter UCPTbreakMode you...
Page 33: ...the receive time on nviDriveValue or nviGroupValue if the respective SCPTmaxRcvTime is not 0 in_alarm Protection position taken with unknown cause analog to nvoFire The status display should be reset...
Page 34: ...ule in groups In this way dampers of the same fire compartment can be controlled together As with direct damper control a heartbeat for failure detection can be set for the input Interface description...
Page 35: ...detected the dampers will be driven in safety position and return state comm_failure Type SNVT_time_sec SNVT 107 Range of values 0 6553 4 Seconds 0 no heartbeat control Presetting no heartbeat contro...
Page 36: ...um of the decimal values is 240 for the UCPTfcGroupMembers Receipt verification The parameter SCPTmaxRcvTime specifies the time after which a new telegram is expected via nviGroupValue In this way tel...
Page 37: ...t DECT digital enhanced cordless telecommunications DIN Deutsches Institut f r Normungen e V German Institute for Standardization D Sub 9pole design of a connector system for data connections EN Europ...
Page 38: ...e application NV network variable PDA personal digital assistent Plug in tool to configure commission and log components of applications Ressource Files files including definitions of interface compon...
Page 39: ...32 bit transmitter identification for wireless transmitters based on EnOcean technology UCPT user configuration property type UNVT user network variable type VDE VDE Verband der Elektrotechnik Elektr...