Spark Fire Ribbon Installation & Operation Manual Download Page 7

 

INSTALLATION REQUIREMENTS 

The gas fireplace is shipped with a 

3/8” 

tube OD (male) connection.  The gas supply piping should have a 

separate gas shutoff valve and a 

1/8” 

NPT plugged tapping upstream of the valve. The stove and its main 

control valve must be disconnected from the gas supply piping system during any pressure testing of that 

system at test pressures in excess of 1/2 psi (3.5 kPa). The stove must be isolated from the gas supply pip-

ing system by closing the main control valve during any pressure testing of the gas supply system at test 

pressures equal to or less than 1/2 psi (3.5 kPa).  After the gas supply has been connected, use a commercial 

gas leak detector or apply a soapy water solution to all the fittings to check for gas leaks.  Never use a 

flame to test for leaks.   

REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS 

This product must be installed by a licensed plumber or gas fitter when installed within the Com-

monwealth of Massachusetts.  If this appliance is installed in a dwelling, building or structure used in 

whole or in part for residential purposes and the installation includes a horizontal vent termination 

that is less than seven (7) feet above the finished grade in the area of the venting, including but not 

limited to decks and porches, a hard-wired carbon monoxide detector with an alarm and battery 

back-up must be installed on the floor level of the dwelling, building or structure where the appli-

ance is to be installed. 
Additionally, a hard-wired or battery operated carbon monoxide detector with an alarm must be in-

stalled on each additional level of the dwelling, building or structure served by the appliance. It shall 

be the responsibility of the property owner to secure the services of qualified licensed professionals 

for the installation of hard-wired carbon monoxide detectors. 

In the event that the horizontally vented appliance is installed in a crawl space or attic, the hard-

wired carbon monoxide detector with alarm and battery back-up may be installed on the next adja-

cent floor level. 
In the event that this requirement cannot be met at the time of completion of the installation of the 

appliance, the owner shall have a period of thirty (30) days to comply with the requirement. Howev-

er, during said thirty (30) day period, a battery operated carbon monoxide detector with alarm must 

be installed. 
Each carbon monoxide detector as required in accordance with the above provisions must comply 

with NFPA 720 and be ANSI/UL 2034 and IAS certified. 
In addition when the vent termination is less than seven (7) feet above finished grade a metal or plas-

tic identification plate must be permanently mounted to the exterior of the building at a minimum 

height of eight (8) feet above grade directly in line with the exhaust vent terminal.  The sign shall 

read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW.  KEEP 

CLEAR OF ALL OBSTRUCTIONS”. 
A COPY OF THESE INSTRUCTIONS PLUS ALL VENTING INSTRUCTIONS WHICH IN-

CLUDE PARTS LISTS, AND/OR ALL VENTING DESIGN INSTRUCTIONS MUST REMAIN 

WITH THE STOVE AT THE COMPLETION OF THE INSTALLATION. 
ATTENTION INSTALLERS:  Mark below which venting system was used in the installation.  These 
instructions must remain with the 

 

Installation & Operation Manual.  

 
 Simpson DuraVent GS/PRO

®

                   Selkirk Direct-Temp

®

 

        

      

           

 

 

ICC Direct Vent

 

Summary of Contents for Fire Ribbon

Page 1: ......

Page 2: ...reil peut tre install dans une maison pr fabriqu e mobile d j install e demeure si kes r glements locaux le permettent Cet appareil doit tre uniquement avec las type de gaz indiqu sur la plaque signal...

Page 3: ...NSTALLATION RECORD FORM 45 WARRANTY INFORMATION 46 TABLE OF CONTENTS WE STRONGLY SUGGEST THAT YOU READ THIS MANUAL THOROUGHLY BEFORE BEGININNG THE INSTALLATION OF THE DIRECT VENT GAS FIREPLACE ALT HOU...

Page 4: ...m and any gas control which has been under water Due to high temperatures the appliance should be located out of traffic and away from furniture and draperies Children and adults should be alerted to...

Page 5: ...ded that the pilot flame be turned off if the appliance will not be in use for an extended period of time This appliance is equipped for use with the fuel type indicated on the rating plate This appli...

Page 6: ...construction are listed below In addition access to the gas supply must be considered The location of the fireplace will also affect the venting requirements and you must be certain the location will...

Page 7: ...stalled on each additional level of the dwelling building or structure served by the appliance It shall be the responsibility of the property owner to secure the services of qualified licensed profess...

Page 8: ...directly through standard 2 X 4 or 2 X 6 construction exterior wall to a horizontal vent termination cap The vent starter pipe has been designed to accommodate those two common installations without t...

Page 9: ...vent properly Elbows will also be required for those installations However in stallations are limited to a maximum of four 90 elbows or 45 elbow equivalents 4 Note Two 45 elbows equal one 90 elbow 5...

Page 10: ...2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 17 16 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 16 15 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D...

Page 11: ...2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 16 15 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 15 14 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D...

Page 12: ...APS HAVE BUILT IN VERTICAL RISE THAT MUST BE COUNTED D TOTAL NUMBER OF 90 ELBOWS _______ NOTE SNORKELS COUNT AS 2 90 ELBOWS E TOTAL NUMBER OF 45 ELBOWS _______ TERMINATION CAP TYPE HORIZONTAL VERTICAL...

Page 13: ...ust Restrictor Required D Air Restrictor Tabs Open 2 A Fuel LP Gas B Total Vertical Vent Rise 2 feet C Total Horizontal Vent Run Actual 10 feet D 90 Elbows Needed 2 E 45 Elbows Needed 0 F Total 90 Elb...

Page 14: ...ERTICAL TERMINATION The illustration below shows some of the many ways the fireplace may be installed in the home This includes interior and exterior wall installations corner installations and horizo...

Page 15: ...15 VENT TERMINAL CLEARANCES Venting terminals shall not be recessed into a wall or siding...

Page 16: ...during assembly 3 Next remove all remaining packaging materials from the carton 4 Lift the firebox and the fireplace mounting plate as a unit up and out of the carton The best place to lift is at sid...

Page 17: ...pipe and to allow for installation of the vent heat shields that are provided with the fireplace Follow the hole size requirements that are provided below exactly to avoid problems If the location yo...

Page 18: ...ll covering e g sheetrock or plas ter and lath outer wall sheathing and outer wall covering and any adjacent internal wall materials like insulation 2 Scribe a 10 1 2 diameter hole around the vent pas...

Page 19: ...through hole 6 Building codes in your area may require that you add blocking above and below the vent opening The blocking should be above and below the 10 1 2 vent opening you made in the wall and sh...

Page 20: ...should be reconstructed to provide the needed support 3 Before the mounting plate can be lagged to the wall the two tabbed sections of the telescoping vent pipe heat shields that you set aside earlier...

Page 21: ...nches 13 Wrap your fingers around the frame and hold the glass and frame together while you lift the frame up and out of the lower glass retainer Set the glass and frame assembly aside in a safe place...

Page 22: ...maintain the most symmetrical pattern pos sible The first tabs bent must be opposite each other and ori ented horizontally If only one tab is specified orient the ring over the pilot holes so the spli...

Page 23: ...nction simply to keep the bot tom of the fireplace from moving Refer to the adjacent illustration 24 If the fireplace is properly positioned on the brack ets the vent starter pipe and vent heat shield...

Page 24: ...zontal Vent Termination and the wall as shown 4 Slip the inner and outer vent termination pipes on to the vent starter pipe taking care to align the in ner and outer pipes to prevent damage 5 Slide th...

Page 25: ...imum of 10 feet of horizontal run If more than two 90 elbows or equivalent 45 elbows are needed for your installation the maximum amount of horizontal run allowed is reduced See the venting section st...

Page 26: ...gas supply line where it penetrates the wall fireplace mounting plate and the inlet to the regulator on the fireplace This will allow gas to be shut off to the fireplace by simply removing the firepl...

Page 27: ...position and tighten the thumb screw to se cure 7 The remote handset is powered by three AAA bat teries The access panel is located on the back of the handset and simply snaps open to provide access...

Page 28: ...ors includes a gasket that covers the full bottom surface Use care in handling the relief door to avoid damage to the gasket material 2 The first illustration below shows the relief openings and relie...

Page 29: ...left to right 3 Once the bottom edge is in place move your fingers out of the way and press the top of the frame against the firebox while pushing down to be sure the frame is fully engaged in the fra...

Page 30: ...l four philips head screws 7 Position the right side panel so it aligns with the three PEM nuts on the mounting plate and the front PEM nut on the top panel Align the rear and top panel edges with the...

Page 31: ...two surround brackets onto the forward detent of the mating brackets on the fire place top You might find it easier to engage one bracket and then the other Lower the surround until both bracket sets...

Page 32: ...ings The Remote Handset can also be used to control the appliance thermostatically 8 Press and hold the button on the Remote Handset or optional Wall Switch to set the appliance to Pilot flame only 9...

Page 33: ...33...

Page 34: ...n page 32 and the image at the bottom of this page LIGHTING OPERATION AND RATING INFORMATION The Lighting Operation and Rating information is lo cated on a plate under the firebox To access the plate...

Page 35: ...valve on the gas supply line to the appliance Remove all batteries from the receiver as well as the battery from the handset Automatic Shut Off in certain conditions Your fireplace s remote control i...

Page 36: ...ON APPLIANCE TO TURN OFF APPLIANCE When pilot ignition is confirmed motor turns auto matically to maximum flame height CAUTION On the valve turn MAN knob on the ON full counterclockwise position Simu...

Page 37: ...or simply wait to return to MAN mode Briefly pressing the SET button changes the mode of operation in the following order and back to MAXITROL GV60 CONTROL SYSTEM NOTE Manual mode can also be reached...

Page 38: ...all flame but ton to decrease Daytime Set Temperature Press OFF or simply wait to complete pro gramming SETTING THE NIGHTTIME SETBACK TEMPERATURE Default Settings moon OFF TEMP Briefly press SET butto...

Page 39: ...sun is displayed and the time flashes Press large flame button to set the hour Press small flame button to set the minutes SETTING P1 OFF TIME Briefly press SET button o scroll to TIMER P1 moon while...

Page 40: ...power in the receiver the system shuts off completely NOTE This does not apply when the power supply is interrupted No change in pilot The appliance shuts off completely when it is continually in pil...

Page 41: ...in the frame so it is very important to support both the glass and the frame when handling Place your thumbs on the outside of the glass frame and wrap your fingers around the frame and onto the glass...

Page 42: ...aning the Burner and Firebox During the annual inspection and maintenance appointment the service person should clean the burner and firebox To gain access to the firebox and burner follow the instruc...

Page 43: ...nnections Other __________________________ MAINTENANCE LOG Date of Service ____________________ Serviced By ______________________ Service Performed Inspect Venting Clean Burner Firebox Clean Control...

Page 44: ...Module Maxitrol M46 504 Burner Module LP 46P 901 Wall Switch Panel optional M46 505 Firebox Panel Rear 46 512 Remote Handset Maxitrol M46 507 Firebox Panel Left 46 513 Gas Valve Maxitrol M46 515 Fire...

Page 45: ...45 CONTROL SCHEMATIC Caution Label all wires prior to disconnection when servicing the controls Wiring errors can cause improper and dangerous operation Verify proper operation after servicing...

Page 46: ...ow that describes the details of the installation Having this writ ten record of installation information available will greatly expedite trouble shooting should any problem arise with your stove The...

Page 47: ...47 SPARK Modern Fires 99B Greenwood Ave Bethel CT 06801 P 866 938 3846 F 203 798 8661 www sparkfires com...

Page 48: ...48 V2 8 15 14 Model ________________________________ Serial _________________________________ Date Purchased __________________________ Date Installed ____________________________...

Reviews: