INSTALLATION REQUIREMENTS
MINIMUM CLEARANCES TO COMBUSTIBLE CONSTRUCTION
Fireplace Surround to L. Side Wall
6”
(152mm) Fireplace Surround to Ceiling
8”
(203mm)
Fireplace Surround to R. Side Wall
6”
(152mm)
Fireplace Surround to Rear Wall
0”
(0mm)*
Fireplace Surround to Corner Wall
6”
(152mm)
Fireplace Surround to Floor
3”
(76mm)**
Vent Pipe to Adjacent Materials
1.5”
(38mm)
*Mounting plate bosses contact the wall
**The minimum required clearance to be maintained from the fireplace Surround to combustible flooring
is measured from the top surface of carpeting, tile, etc.
Several issues must be addressed when selecting a suitable location for your
fireplace. The mini-
mum clearances to combustible construction are listed below. In addition, access to the gas supply must be
considered. The location of the fireplace will also affect the venting requirements and you must be certain
the location will allow compliance with the venting requirements shown on page 8
.
You must also insure
that your installation provides adequate accessibility clearance for servicing and proper operation.
Installation and repair should be done by a qualified service person. The appliance should be inspected
before use and at least annually by a professional service person. More frequent cleaning may be required
due to excessive lint from carpeting, bedding material, etc. It is imperative that the control compartment,
burners and circulating air passageways of the appliance be kept clean.
WALLS
A =
6”
(152mm)
A
A
C =
8”
(203mm)
D =
3”
(76mm)
CEILING
C
FLOOR
D
E =
3/8”
(10mm)
WALL
AIR SPACE BEHIND MOUNTING PLATE