Spark Fire Ribbon Installation & Operation Manual Download Page 41

41 

 

A qualified service agency should conduct an annual inspection and maintenance of your 

 

includ-

ing the overall installation and venting to keep it running safely.  The following procedures should be per-
formed only by a qualified service person. The gas supply should be turned off and the stove should be 
completely cool whenever a maintenance procedure is performed. All parts of the appliance that are removed for 
servicing must be replaced prior to operation.   

WARNING:    Do  not  operate  the  appliance  with  the  glass  front  removed,  cracked  or    broken. 

Replacement of the glass should be done by a qualified service person.

 

WARNING:  Use only glass assembly, P/N 46-510 which includes the glass panel, frame and gasket.  

Do not use substitute materials.  Do not strike or slam the glass front. The appliance area must be 

kept clear and free from combustible materials, gasoline and other flammable vapors and liquids. 
 
CAUTION: DO NOT OPERATE WITH BROKEN GLASS 
 
REPLACING THE GLASS

 

The glass mounting system consists of the glass panel, special glass gasket and the metal glass frame.  

Should the glass need to be replaced, you must replace the entire glass/glass frame assembly (PN 46-510). 

See page 46 for information on obtaining replacement parts. Use the following procedure and refer to the 

illustrations on page 29 of this manual. 

1.  Turn the fireplace completely off and allow it to cool to room temperature. 

2.  Remove the fireplace surround. See instructions on page 31. 

3.  If the glass is broken, be sure to wear gloves and eye protection. 

4.  Remove the glass frame fasteners from the top edge of the glass frame. 

5.  This will allow the glass frame to tip slightly forward. The glass may be  loose in the frame, so it is very 

important to support both the glass and the frame when handling.  Place your thumbs on the outside of 

the glass frame and wrap your fingers around the frame and onto the glass.  Squeeze the frame and glass 

while moving. Carefully lift the glass frame and glass up and off the fireplace.  Set the glass and frame 

aside on a padded surface.  If the glass is broken, do this over spread out newspaper to catch all loose 

material.  Wrap the old glass frame, glass and gasket in several layers of newspaper and discard.   

Installing the replacement glass/glass frame assembly. 

1.  Unpack the new glass/glass frame assembly taking care when handling. 

2.  Carefully pick up the glass and glass frame assembly by grasping the sides of the frame and using your 

thumbs and fingers to hold the glass in place within the gasket and frame. 

3.  With the glass frame (and glass) at a slight angle (leaving room for your fingers between the frame and 

the firebox) insert the bottom edge of the frame into the frame retainer located on the bottom front of 

the firebox.  Take care to center the frame from left to right.  Once the bottom edge is in place, move 

your fingers out of the way and press the top of the frame against the firebox while pushing down to be 

sure the frame is fully engaged in the frame retainer.  Hold the frame in place with one hand and rein-

stall the glass frame fasteners, leaving them loose. 

4.  Tighten the glass frame fasteners in stages working from the center out.  Continue the process until all 

fasteners are uniformly tight.  Do not over-tighten the fasteners. 

5.  Replace the fireplace surround. See instructions on page 31. 

CLEANING THE GLASS 
WARNING:  Never clean the glass while it is hot.  Do not use abrasive cleaners or cleaners containing 

ammonia.   
NOTE:  A micro-fiber cleaning cloth and plain water is recommended by the glass manufacturer. 

 

MAINTENANCE 

Summary of Contents for Fire Ribbon

Page 1: ......

Page 2: ...reil peut tre install dans une maison pr fabriqu e mobile d j install e demeure si kes r glements locaux le permettent Cet appareil doit tre uniquement avec las type de gaz indiqu sur la plaque signal...

Page 3: ...NSTALLATION RECORD FORM 45 WARRANTY INFORMATION 46 TABLE OF CONTENTS WE STRONGLY SUGGEST THAT YOU READ THIS MANUAL THOROUGHLY BEFORE BEGININNG THE INSTALLATION OF THE DIRECT VENT GAS FIREPLACE ALT HOU...

Page 4: ...m and any gas control which has been under water Due to high temperatures the appliance should be located out of traffic and away from furniture and draperies Children and adults should be alerted to...

Page 5: ...ded that the pilot flame be turned off if the appliance will not be in use for an extended period of time This appliance is equipped for use with the fuel type indicated on the rating plate This appli...

Page 6: ...construction are listed below In addition access to the gas supply must be considered The location of the fireplace will also affect the venting requirements and you must be certain the location will...

Page 7: ...stalled on each additional level of the dwelling building or structure served by the appliance It shall be the responsibility of the property owner to secure the services of qualified licensed profess...

Page 8: ...directly through standard 2 X 4 or 2 X 6 construction exterior wall to a horizontal vent termination cap The vent starter pipe has been designed to accommodate those two common installations without t...

Page 9: ...vent properly Elbows will also be required for those installations However in stallations are limited to a maximum of four 90 elbows or 45 elbow equivalents 4 Note Two 45 elbows equal one 90 elbow 5...

Page 10: ...2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 17 16 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 16 15 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D...

Page 11: ...2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 16 15 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 15 14 D 1 1 2 D 1 1 2 D 1 1 2 D 1 1 2 D...

Page 12: ...APS HAVE BUILT IN VERTICAL RISE THAT MUST BE COUNTED D TOTAL NUMBER OF 90 ELBOWS _______ NOTE SNORKELS COUNT AS 2 90 ELBOWS E TOTAL NUMBER OF 45 ELBOWS _______ TERMINATION CAP TYPE HORIZONTAL VERTICAL...

Page 13: ...ust Restrictor Required D Air Restrictor Tabs Open 2 A Fuel LP Gas B Total Vertical Vent Rise 2 feet C Total Horizontal Vent Run Actual 10 feet D 90 Elbows Needed 2 E 45 Elbows Needed 0 F Total 90 Elb...

Page 14: ...ERTICAL TERMINATION The illustration below shows some of the many ways the fireplace may be installed in the home This includes interior and exterior wall installations corner installations and horizo...

Page 15: ...15 VENT TERMINAL CLEARANCES Venting terminals shall not be recessed into a wall or siding...

Page 16: ...during assembly 3 Next remove all remaining packaging materials from the carton 4 Lift the firebox and the fireplace mounting plate as a unit up and out of the carton The best place to lift is at sid...

Page 17: ...pipe and to allow for installation of the vent heat shields that are provided with the fireplace Follow the hole size requirements that are provided below exactly to avoid problems If the location yo...

Page 18: ...ll covering e g sheetrock or plas ter and lath outer wall sheathing and outer wall covering and any adjacent internal wall materials like insulation 2 Scribe a 10 1 2 diameter hole around the vent pas...

Page 19: ...through hole 6 Building codes in your area may require that you add blocking above and below the vent opening The blocking should be above and below the 10 1 2 vent opening you made in the wall and sh...

Page 20: ...should be reconstructed to provide the needed support 3 Before the mounting plate can be lagged to the wall the two tabbed sections of the telescoping vent pipe heat shields that you set aside earlier...

Page 21: ...nches 13 Wrap your fingers around the frame and hold the glass and frame together while you lift the frame up and out of the lower glass retainer Set the glass and frame assembly aside in a safe place...

Page 22: ...maintain the most symmetrical pattern pos sible The first tabs bent must be opposite each other and ori ented horizontally If only one tab is specified orient the ring over the pilot holes so the spli...

Page 23: ...nction simply to keep the bot tom of the fireplace from moving Refer to the adjacent illustration 24 If the fireplace is properly positioned on the brack ets the vent starter pipe and vent heat shield...

Page 24: ...zontal Vent Termination and the wall as shown 4 Slip the inner and outer vent termination pipes on to the vent starter pipe taking care to align the in ner and outer pipes to prevent damage 5 Slide th...

Page 25: ...imum of 10 feet of horizontal run If more than two 90 elbows or equivalent 45 elbows are needed for your installation the maximum amount of horizontal run allowed is reduced See the venting section st...

Page 26: ...gas supply line where it penetrates the wall fireplace mounting plate and the inlet to the regulator on the fireplace This will allow gas to be shut off to the fireplace by simply removing the firepl...

Page 27: ...position and tighten the thumb screw to se cure 7 The remote handset is powered by three AAA bat teries The access panel is located on the back of the handset and simply snaps open to provide access...

Page 28: ...ors includes a gasket that covers the full bottom surface Use care in handling the relief door to avoid damage to the gasket material 2 The first illustration below shows the relief openings and relie...

Page 29: ...left to right 3 Once the bottom edge is in place move your fingers out of the way and press the top of the frame against the firebox while pushing down to be sure the frame is fully engaged in the fra...

Page 30: ...l four philips head screws 7 Position the right side panel so it aligns with the three PEM nuts on the mounting plate and the front PEM nut on the top panel Align the rear and top panel edges with the...

Page 31: ...two surround brackets onto the forward detent of the mating brackets on the fire place top You might find it easier to engage one bracket and then the other Lower the surround until both bracket sets...

Page 32: ...ings The Remote Handset can also be used to control the appliance thermostatically 8 Press and hold the button on the Remote Handset or optional Wall Switch to set the appliance to Pilot flame only 9...

Page 33: ...33...

Page 34: ...n page 32 and the image at the bottom of this page LIGHTING OPERATION AND RATING INFORMATION The Lighting Operation and Rating information is lo cated on a plate under the firebox To access the plate...

Page 35: ...valve on the gas supply line to the appliance Remove all batteries from the receiver as well as the battery from the handset Automatic Shut Off in certain conditions Your fireplace s remote control i...

Page 36: ...ON APPLIANCE TO TURN OFF APPLIANCE When pilot ignition is confirmed motor turns auto matically to maximum flame height CAUTION On the valve turn MAN knob on the ON full counterclockwise position Simu...

Page 37: ...or simply wait to return to MAN mode Briefly pressing the SET button changes the mode of operation in the following order and back to MAXITROL GV60 CONTROL SYSTEM NOTE Manual mode can also be reached...

Page 38: ...all flame but ton to decrease Daytime Set Temperature Press OFF or simply wait to complete pro gramming SETTING THE NIGHTTIME SETBACK TEMPERATURE Default Settings moon OFF TEMP Briefly press SET butto...

Page 39: ...sun is displayed and the time flashes Press large flame button to set the hour Press small flame button to set the minutes SETTING P1 OFF TIME Briefly press SET button o scroll to TIMER P1 moon while...

Page 40: ...power in the receiver the system shuts off completely NOTE This does not apply when the power supply is interrupted No change in pilot The appliance shuts off completely when it is continually in pil...

Page 41: ...in the frame so it is very important to support both the glass and the frame when handling Place your thumbs on the outside of the glass frame and wrap your fingers around the frame and onto the glass...

Page 42: ...aning the Burner and Firebox During the annual inspection and maintenance appointment the service person should clean the burner and firebox To gain access to the firebox and burner follow the instruc...

Page 43: ...nnections Other __________________________ MAINTENANCE LOG Date of Service ____________________ Serviced By ______________________ Service Performed Inspect Venting Clean Burner Firebox Clean Control...

Page 44: ...Module Maxitrol M46 504 Burner Module LP 46P 901 Wall Switch Panel optional M46 505 Firebox Panel Rear 46 512 Remote Handset Maxitrol M46 507 Firebox Panel Left 46 513 Gas Valve Maxitrol M46 515 Fire...

Page 45: ...45 CONTROL SCHEMATIC Caution Label all wires prior to disconnection when servicing the controls Wiring errors can cause improper and dangerous operation Verify proper operation after servicing...

Page 46: ...ow that describes the details of the installation Having this writ ten record of installation information available will greatly expedite trouble shooting should any problem arise with your stove The...

Page 47: ...47 SPARK Modern Fires 99B Greenwood Ave Bethel CT 06801 P 866 938 3846 F 203 798 8661 www sparkfires com...

Page 48: ...48 V2 8 15 14 Model ________________________________ Serial _________________________________ Date Purchased __________________________ Date Installed ____________________________...

Reviews: