32
Figure 4.3.2 DC setting interface
DC withstand voltage (DC) test parameters are described below
VOLT
:
0.050
~
6.000kV
High voltage test voltage value
UPPER
:
0.1uA
~
10.00mA
Current upper limit
0.1uA
~
5.00mA
Current upper limit
LOWR
:
0. 1uA
~
10.00mA
Current lower limit, should be less than the UPPER limit
0. 1uA
~
5.00mA
Current lower limit, should be less than the UPPER limit
OFF
LOWR is not required
TIME
:
0.1
~
999.9S
test time, the test is end when the time is up
OFF
Unlimited test time
RISE
:
0.1
~
999.9S
Test voltage rise time
OFF
Default=0.1S
,
Integration with test time
FALL
:
0.1
~
999.9S
Test voltage fall time
OFF
End of test stop voltage output
WAIT
:
0.1
~
999.9S
DC charging wait time
OFF
Components do not need to be charged
ARC
:
0.1
~
20.0 mA
maximum DC arc current
OFF
ARC is not required
RAMP
:
ON
When the voltage rises, to judge the current upper limit allowed
OFF
Do not judge current upper limit
Note:
1.
After the DC test is over, the instrument will automatically perform a 0.2 second
rapid discharge.
2.
During the waiting time, the instrument does not judge the current upper limit, but
the short circuit detection circuit is still working.
4.3.3
IR Insulation resistance test parameter setting
Move the cursor to a test condition, press "F1~F6" to modify the current test condition or
data.
The setting interface is as follows: (Figure 4.3.3)