PAT-806-IT
– USER MANUAL
10
- for TN mains
- for IT mains
Notes:
- When the network voltage is below 187 V the meter turns off automatically.
Additional information displayed by the meter
,
and
an acoustic signal
Lack of PE continuity, the measurements are blocked (mes-
sage
blinks).
,
and
an acoustic signal
Voltage U
N-PE
> 25 V, the measurements are blocked (the
voltage value blinks), ), for IT mains, the measurements are
blocked for voltage L-PE >180V.
and
an acoustic signal
Mains voltage > 265 V, measurements are blocked.
Exchanged L and N, measurements are possible.
3.4 General Settings - MENU
By pressing
SET
button the user enters the mode where the following actions are available:
setting date and time
communicating with PC
updating firmware
operating the meter with a bar-code reader and printer
transferring data to a pen-drive
setting nominal network voltage
setting current values in the measurement of R
PE
on IEC lead.