PAT-806-IT
– USER MANUAL
6
2 General description and features of the instrument
PAT-806-IT digital meter is intended to measure the basic parameters of portable electrical de-
vices (power tools, household appliances, etc.) important for their safety: protective conductor re-
sistance, insulation resistance, continuity of connections, the leakage current.
The meter may be used to test the equipment, in accordance with the following standards:
EN 60745-1 Hand-held motor-operated electric tools. Safety. Part 1: General requirements.
EN 61029 Safety of transportable motor operated electric tools. General requirements.
EN 60335-1 Household and similar electrical appliances. Safety. Part 1: General requirements.
EN 60950 Information technology equipment
– Safety- Part 1: General requirements.
EN 60974-4 Arc welding equipment - Part 4: Periodic inspection and testing
VDE 0404-
1 Prüf- und Messeinrichtungen zum Prüfen der elektrischen Sicherheit von elektri-
schen Geräten. Teil 1: Allgemeine Anforderungen.
VDE 0404-
2 Prüf- und Messeinrichtungen zum Prüfen der elektrischen Sicherheit von elektri-
schen Geräten. Teil 2: Prüfeinrichtungen für Prüfungen nach Instandsetzung, Änderung oder für
Wiederholungsprüfungen.
VDE 0701-
0702 Prüfung nach Instandsetzung, Änderung elektrischer Geräte. Wiederho-
lungsprüfung elektrischer Geräte. Allgemeine Anforderungen für die elektrische Sicherheit.
Basic functions of the instrument:
Measurement of network voltage and frequency
Rated voltage measurement on welding equipment
Checking the resistance of L-N circuit
Checking the fuse
Measurement of protective conductor resistance (Protection class - I):
technical measurement method
measurement with sinusoidal current of network frequency and values: 200 mA, 10 A and
25 A
adjustable measurement time
adjustable upper limit in the range of: 10
mΩ …1.99 Ω with resolution 0.01 Ω
Measurement of insulation resistance:
three test voltages: 100 V, 250 V and 500 V
measurement of insulation resistance up to 600 M
automatic discharge of the capacitance of tested object after the insulation resistance meas-
urement is completed
adjustable measurement time
adjustable lower limit within the range of 0.1
MΩ ….9.9 MΩ with resolution of 0.1 MΩ
three point measurement of insulation resistance on welding equipment
Measurement of substitute leakage current:
adjustable measurement time
adjustable upper limit in the range of: 0.01 mA ... 9.9 mA with resolution of 0.01 mA/0.1 mA
Measurement of PE leakage current
adjustable measurement time
adjustable upper limit in the range of: 0.01 mA ... 9.9 mA with resolution of 0.01 mA/0.1 mA