ELIXO 2000 230V RTS
EN
8
Copyright
©
2018 SOMFY ACTIVITES SA. All rights reserved.
Menu
Sub-menu
Val.
Description
1
Semi-automatic
• pressing the button on the remote control while the gate is open-
ing will stop the gate
• pressing a button on the remote control during closing causes it
to reopen
With following
LoGIc
parameter
setting:
tcA
= 0
IbL oPEn
= 0
IbL tcA
= 0
Automatic
In automatic mode, the final position of the gate will always be the
closed position.
Operation in automatic closing mode is only authorised if photoelec-
tric cells with autotest function are installed (see Fig. 19).
• the gate closes automatically aer the timeout programmed in the
PArAM
/
tcA
menu
• pressing the button on the remote control during opening has no
effect,
• pressing a button on the remote control during closing causes it
to reopen
• if an obstacle is located within the detection zone of the cells
during the timeout, the timeout is reinitialised once the cells are
cleared
With following
LoGIc
parameter
setting:
tcA
= 1
IbL oPEn
= 1
IbL tcA
= 1
Aut cell blocking
During and aer gate opening, movement in front of the cells (safe
closure) will close the gate aer a short timeout (fixed at 3 seconds).
If there is no movement in front of the cells, the gate will close
automatically aer the closing timeout programmed in the
PArAM
/
tcA
menu.
With following
LoGIc
parameter
setting:
tcA
= 1
IbL oPEn
= 1
IbL tcA
= 1
FASt cLS.
=1
2
Not used
PrE-
ALArM
0
Without notice before movement
1
With 3 s warning prior to movement
hoLd-to-
rUn
0
Pulse-controlled operation
1
"Dead man" operation
• Input 19 configured as OPEN UP
• Input 20 configured as CLOSED UP
Controlled by maintained action
Attention
Safety devices inactive
IbL oPEn
0
Pulse of radio-configured inputs takes effect during opening
1
Pulse of radio-configured inputs does not take effect during opening
IbL tcA
0
Pulse of radio-configured inputs takes effect during TCA opening
1
Pulse of radio-configured inputs does not take effect during TCA pause
oPEn In
othEr
dIrEct.
0
Gate opens towards the right
1
Gate opens towards the le
SAFE 1
2
Cell safety input active without autotest during opening only
3
Cell safety input active with autotest during opening only
SAFE 2
4
Cell safety input active without autotest during closing only
5
Cell safety input active with autotest during closing only
SAFE 3
6
Safety edge safety input active without autotest
7
Safety edge safety input active with autotest
AUX 3
(auxiliary 3)
1
Gate open indicator light output
Contact closed when opening and when the gate is open, intermittent during closing, open with gate closed
2
Courtesy lighting command output
Contact closed for 90 seconds aer the last movement
DEFAULt
Control unit reset to factory configuration
LAnGUAGE
ItA
Attention
Do not modify the display language on the interface.
In the installation manual, the names of the menus and sub-menus
are in English only.
FrA
dEU
EnG
Default value
ESP
AutoSEt
Gate travel auto-programming started
StAt
vErS
Control unit soware version
n. cYcLES
Number of cycles (per hundreds)