animeo KNX/EIB 4 AC MoCo • REF. 5050779 -
9/31
2. If the device with the ETS has already been programmed.
If the device with the ETS has already been programmed, a reset to delivery
status is not possible over the Reset/Prog button. Over the function “Unload”
in the ETS all settings of the device can be reset to delivery status. The Reset/
Prog button can then be used again.
Communication objects
A maximum of 100 communication objects are available, which however cannot be used at one time.
Maximally 95 group addresses can be linked.
4
No.
Objekt name
Type
Description
0
Motor 1 UP/DOWN, CLOSE/OPEN
1 Bit (EIS 7)
If a telegram with the value “0” is received on this communication object,
the appropriate blind goes up or the window closes. If a telegram with the
value “1” is received, the appropriate blind goes down or the window
opens. At expiration of the adjusted running time for the UP and DOWN
direction the relays of the outputs are activated.
1
Motor 2 UP/DOWN, CLOSE/OPEN
1 Bit (EIS 7)
2
Motor 3 UP/DOWN, CLOSE/OPEN
1 Bit (EIS 7)
3
Motor 4 UP/DOWN, CLOSE/OPEN
1 Bit (EIS 7)
4
Motor 1 STEP / STOP
1 Bit (EIS 7)
For venetian blinds:
If the venetian blind is in a fully moving process, the
venetian blind stops with the receipt of a telegram on the appropriate
object, independently whether a telegram with the value “0“ or “1“ is
received. If the venetian blind is in passive state, a step will be executed
whereas with the receipt of a telegram with the value “1” the slat will
close and with the receipt of a telegram with the value “0” the slat will
open. The step length is de-fined in the parameter settings for the
appropriate motor.
For screens, roller blinds, awnings and windows:
If one of these end products is in a fully moving process, the end product
stops with the receipt of a telegram on the appropriate object, indepen-
dently of whether a telegram with the value “0“ or “1“ is received. If one
of these end products is in passive state, then with the receipt of a
telegram on one of these communication objects no action is executed.
5
Motor 2 STEP / STOP
1 Bit (EIS 7)
6
Motor 3 STEP / STOP
1 Bit (EIS 7)
7
Motor 4 STEP / STOP
1 Bit (EIS 7)
8
Motor 1 Position UP / DOWN
1 Byte (EIS 6)
If one of these communication objects receives a telegram, the appropriate
blind will go into the position which is defined by the received value.
“0“ = UP “255“ = DOWN
For venetian blinds:
If the position is reached, the same slat angle starts
up in which the venetian blind was previously.
9
Motor 2 Position UP / DOWN
1 Byte (EIS 6)
10
Motor 3 Position UP / DOWN
1 Byte (EIS 6)
11
Motor 4 Position UP / DOWN
1 Byte (EIS 6)
12
Motor 1 Slat position
1 Byte (EIS 6)
For venetian blinds:
If one of these communication objects receives a
telegram, the appropriate slat will go to that position which is defined by
the received value. If the venetian blind is in full moving process while
receiving a telegram on the appropriate object, the position of the slat will
be started up when the drive is finished. Depending on the parameter set-
ting on parameter card „General“ the position is defined
as follows:
“255“ = slat maximal closed /
“0“ = slat maximal reversed
or
“0“ = slat maximal closed /
“255“ = slat maximal reversed
13
Motor 2 Slat position
1 Byte (EIS 6)
14
Motor 3 Slat position
1 Byte (EIS 6)
15
Motor 4 Slat position
1 Byte (EIS 6)
value
(0/255)
value
(255/0)