![SOMFY Animeo KNX/EIB DRM Series Installation Manual Download Page 24](http://html1.mh-extra.com/html/somfy/animeo-knx-eib-drm-series/animeo-knx-eib-drm-series_installation-manual_1317536024.webp)
animeo KNX/EIB 4 AC MoCo • REF. 5050779 -
24/31
Basic function
Options:
Venetian blind UP / DOWN
Switch/dry contact
8-Bit value (rising edge)
Dimming
Long operation (dimming) after
Options:
0,5 seconds
0,3 - 5,0 seconds
This parameter defines the operating time of the appropriate switch, which differentiates between sending a switching telegram and a
dimming telegram. If the time is, for example, set at
0,5 seconds
, only with duration of an application which is longer than 0,5 seconds a
dimming telegram is generated. With duration of application which is smaller than
0,5 seconds,
a switching telegram is generated.
Input A/B
Options:
On/Off
Toggle/toggle
This parameter defines the value which is sent with short manipulation of the appropriate input.
On/Off
With a short manipulation of the switch at the input A an “Off” telegram is generated. With a short manipulation of the switch at the input B
an “On“ telegram is generated. These functions can be inverted by changing the wiring.
Toggle/toggle
With every short manipulation of the switch at the input A or B, toggling occurs. This means the value that is in the appropriate switching
object is inverted and then sent.
Contact type input A
Options:
Normally open
Normally closed
Specified over this parameter is the contact type at the local input A. Normally open contact: The contact at the local input is not operated
open and operated closed. Normally closed contact: The contact at the local input is operated opened and not operated closed.
On (“1“)
Off (“0“)
Toggle (“1/0“)