animeo KNX/EIB 4 AC MoCo • REF. 5050779 -
17/31
Step length
Basis 0,05 s (0 - 200)
Options:
2
0 - 200
The confiured time here defines the time for a tilting step. This parameter is visible only if as type of end product either venetian blind with EU
ergonomics or venetian blind with US ergonomics were selected.
Slack compensation
0,05 s (0 - 200)
Options:
0
0 - 200
The time for slack compensation is active as soon as a higher value than “0“ is registered. The time configured here defines the time to add to
the complete tilting time in order to adjust mechanical tolerances. This time is always added with the first UP (reverse/open) command of the
slat if as type of end product either venetian blind with EU ergonomics or venetian blind with US ergonomics were selected.
Security position
Low priority
Options:
Upper end position
Lower end position
Intermediate position 1
Intermediate position 2
Security ignore
Stop
Close window
Open window
Over this parameter the security position “low security” is specified for the appropriate blind. If on one of the communication objects (objects
26-30) a telegram with the value “1” is received, then the appropriate blind moves to the position which is configured in the ETS parameters.
If on one of these communication objects a telegram with the value “0“ is received no action will be executed. Only if in the ETS parameters
“Repeat the last telegram after security (Yes)” is selected, then this action for the appropriate blind will be executed.
If one of these communication objects is active by a telegram with the value “1“ and on one of the communication objects 31-34 (security
position, high priority) a telegram with the value “1“ is received, the appropriate blind moves to the position configured in the ETS parameters
(security position, high priority).
Security position
High priority
Options:
Upper end position
Lower end position
Security ignore
Stop
Close window
Open window
Over this parameter the security position “high security” is specified for the appropriate blind. If on one of the communication objects (objects
31-35) a telegram with the value “1” is received, then the appropriate blind moves to the position configured in the ETS parameters. If on
one of these communication objects a telegram with the value “0 “ is received no action will be executed. Only if in the ETS parameters
“Repeat the last telegram after security (Yes)“ is selected, then this action for the appropriate blind will be executed.
Cyclic monitoring time in seconds (0 - 255)
Options:
0
0 - 255
Cyclic monitoring time is active as soon as a higher value than “0“ is registered and refers to both security objects, low and high priority.
n
With active cyclic monitoring it is to be made certain that the time of the cyclic transmitter is smaller, approx. 1/4 than the configured cyclic
monitoring time for the security objects, low and high priority.
If the default value remains adjusted “0“ the security objects react statically to the values “1” and “0”.