21
Fig.31- Correct
sealing
Fig.32- Incorrect
sealing
* Ensure that the tube bindings do not strangle the tube (narrowing the flow), the inner tube walls
are smooth and free of obstacles, and that the caps do not disturb the air circulation;
* The chimney dome should allow proper air circulation and be placed at least 1 m above the roof
peak or 3 m away from other obstacles. If you need to increase the air circulation, you should
extend the height of the flue;
* Never use the same chimney flue for more than one unit or open fireplace. For shared chimneys,
each flue should individually reach the external outlets at the same level, to ensure that the air
circulation adequately expels the exhaust fumes;
A minimum of 1 m
above the highest
point
Fig. 35– Incorrect
chimney height
Fig. 36– Correct
chimney height
Fig. 33– Incorrect
binding
Fig. 34– Correct
binding
Minimum
distance
equivalent to
the tube
diameter