32
Control Keypad
_____________________________________________________________________________________
7.6.3
Main Parameters
±
page 1
MAIN PARAMETERS
- **** -
Displays in MINIMIZED MODE and MAXIMIZED MODE
(Refer below for changing modes)
Display and default
values
Range Description
Remarks
LANGUAGE:
ENGLISH
SPANISH
GERMAN
FRENCH
ENGLISH
TURKCE
RUSSIAN
(Optional)
6HWV6WDUWHU¶V
language
STARTER FLC
58 AMP.
8
±
1100A
6HWVVWDUWHU¶V
FLC (Full load
current)
6WDUWHU¶V)/&VKRXOGEHDVVKRZQRQVWDUWHU¶V
Name plate. (Refer to section
6.1 on page 22)
MOTOR FLA
58 AMP.
50-100% of
STARTER
FLC
6HWVPRWRU¶V
FLA (Full load
Ampere)
6KRXOGEHSURJUDPPHGDVVKRZQRQPRWRU¶V
name plate.
Note
:
When the RVS-DXM is installed Inside Delta set
MOTOR FLA = <
rated motor current
>/1.73.
RATED POWER
30KW
1-3000KW
6HWVPRWRU¶V
POWER
Rated motor power is used for analog output
reference. When analog card is installed, full
scale of the readings (20mA or 10V as per dip-
switches settings on the analog card) are related
to 200%FLA. (2x rated motor current) or 200% of
rated power or POWER FACTOR.
Refer to section
7.6.9 on page 47 for analog
output programming.
Note
:
POWER FACTOR & POWER measurement only
available in RVS-DXM58A and up.
CONNECTION TYPE
LINE
LINE,
INSIDE
DELTA
6HWV6WDUWHU¶V
connection
type.
Factory preset
±
features and functions when
³,16,'('(/7$´PRGHLVFRQILJXUHG
No Pulse Start.
No Curve selection (CURVE 0!!).
No slow speed.
1RSKDVHVHTXHQFH³RII´PRGH
Refer to section
4.5.3 on page 14 for further
information
RATED LINE VOLT.
400 VOLT
220-690V Sets
rated
LINE
VOLTAGE.
UNDERCURR. TRIP
0% OF FLA
0%=off;
20-90% of
FLA
Sets UNDER
CURRENT
TRIP
protection.
Trips the starter when motor current drops blow
set level for a time longer than UNDER
CURRENT DELAY
UNDERCURR. DELAY
10 SEC.
1-40sec.
Sets the time