28
Control Keypad
_____________________________________________________________________________________
7.5.5
Calibrate Voltage, Current and (Factory Use Only!)
Press the
Mode
and
ź
keys simultaneously.
the LCD will display:
TEST/MAINTENANCE
***OPTIONS***.
Press the
Select
key
five times
.
The LCD will display:
VOLTAGE ADJUST.
X VOLT
Press the
Select
key.
The LCD will display:
CURRENT ADJUST.
5% OF FLC
Press the
Select
key.
The LCD will display (POWER FACTOR & POWER measurement only available in RVS-DXM58A and up):
POWER FACTOR
0.71
Press the
Mode
and
ź
keys simultaneously to exit the TEST/MAINTENANCE mode.
7.6
Mode Pages
8SRQLQLWLDWLRQRIWKHVWDUWHUWKH/&'GLVSOD\VPRWRU¶VRSHUDWLQJFXUUHQW
% OF MOTOR FLA
0%
By pressing the
Mode
key all mode pages can be reviewed:
MAIN PARAMETERS
- **** -
START PARAMETERS
- **** -
STOP PARAMETERS
- **** -
DUAL ADJUSTMENT
PARAMETERS
These pages are skipped if RVS-DXM is programmed to
³0,1,0,=('02'(´DQGDUHVKRZQRQO\LQ³0$;,0,=('02'(´
(Refer to section
7.6.3 on page 32 for information on changing
IURP³0,1,0,=('02'(´WR³0$;,0,=('02'(´
SPECIAL FEATURES
PARAMETERS
FAULT PARAMETERS
- **** -
I/O PROGRAMMING
PARAMETERS
COMM PARAMETERS
- **** -
STATISTICAL DATA
- **** -