Control Keypad
________________________________________________________________________________________
7.6.1
Overview of All Mode Pages and Factory Defaults
Appears only in
MAXIMIZED MODE
(1)
% OF MOTOR FLA
XX%
MAIN PARAMETERS
START PARAMETERS
STOP PARAMETERS
DUAL ADJUSTMENT
PARAMETERS
Refer page 31
Refer page 32
Refer page 36
Refer page 40
Refer page 42
AMP. VOLT
0 0
LANGUAGE:
ENGLISH
SOFT START CURVE
0(STANDARD)
SOFT STOP CURVE
0(STANDARD)
DA: INIT. VOLT.
30%
OPTION CARD
Not Installed
STARTER FLC
58 AMP.
PULSE TIME
0 SEC.
DEC. TIME
0 SEC.
DA: CUR. LIMIT
400% OF FLA
POWER
(2)
MOTOR FLA
58 AMP.
INITIAL VOLTAGE
30 %
FINAL TORQUE
0 (MIN.)
DA: ACC. TIME
10 SEC.
POWER FACTOR
(2)
RATED POWER
30KW
CURRENT LIMIT
400% OF FLA
STORE ENABLE
STOP PARAMETERS
DA: DEC. TIME
0 SEC.
CONNECTION TYPE
LINE
ACC. TIME
10 SEC.
DA: MOTOR FLA
31 AMP.
RATED LINE VOLT.
400 VOLT
MAX. START TIME
30 SEC.
STORE ENABLE
D. ADJ PARAMETERS
UNDERCURR. TRIP
0% OF FLA
NUMBER OF STARTS
10
UNDERCURR. DELAY
10 SEC.
STARTS PERIOD
30 MIN.
O/C
±
SHEAR PIN
850% OF FLA
START INHIBIT
15 MIN.
O/C DELAY
0.5 SEC.
STORE ENABLE
START PARAMETERS
OVERLOAD CLASS
IEC CLASS 10
OVERLOAD PROTECT
ENABLE WHILE RUN
UNDERVOLT. TRIP
75%
UNDERVOLT. DELAY
5 SEC.
OVERVOLT. TRIP
120 %
OVERVOLT. DELAY
2 SEC.
DISPLAY MODE
MINIMIZED
PARAMETERS LOCK
NOT LOCKED
STORE ENABLE
MAIN PARAMETERS
(1) - Refer to section
7.6.3 on page 32
IRULQIRUPDWLRQRQFKDQJLQJIURP³0,1,0,=('02'(´)DFWRU\
GHIDXOWWR³0$;,0,=('02'(´
(2) POWER and POWER FACTOR readings available in RVS-DXM 58A and up.