53
Control Keypad
________________________________________________________________________________________
7.8
Timing Occurrence Table
Timing And Occurrence
Active During
Start
Run
Stop
Soft
Stop
Too many starts
with Start Inhibit period
¥
Electronic Overload
with Curve selection
¥
¥
O/C Shear Pin (Jam)
Starter Protection
±
trip immediately at 850% FLC
¥
¥
¥
Motor Protection
±
trip function
During Start
±
factory set at 850% FLA in less than 1 cycle (*).
¥
¥
During Run
±
adjust. 200
±
850% FLA within 1 cycle (*).
¥
Under current
adjustable time delay
¥
Phase Loss
¥
¥
¥
Phase sequence
¥
Under voltage
with adjustable time delay. Time delay is
RYHUULGHLQFDVHRI³1R
-
9ROW´
¥
¥
¥
Over voltage
with adjustable time delay
¥
¥
¥
Long start time
(Stall protection)
¥
Shorted SCR or Wrong connection
¥
¥
External fault
±
input from a N.O. contact
¥
¥
¥
¥
SCR protection
by Metal Oxide Varistors (MOV)
¥
¥
¥
¥
Starter over-temperature
¥
¥
¥
¥
Starter internal test,
ZKHQ³2Q´/('LVOLW
¥
¥
¥
¥
Motor Insulation test -
Not Available (Consult Factory)
¥
Motor Thermistor
±
Not Available (Consult Factory)
¥
¥
¥
¥