![SolarEdge StorEdge Solution with Backup Installation Manual Download Page 69](http://html1.mh-extra.com/html/solaredge/storedge-solution-with-backup/storedge-solution-with-backup_installation-manual_1313758069.webp)
Figure 30: Connecting to the auto-transformer
1. Use the supplied Allen key to open the 4 screws of the auto-transformer and remove
its cover.
2. Prepare cables and connect as described in the following table:
Recommended
cable type
(min-max AWG)
StorEdge
Connection Unit
connection
Auto-transformer
connection
Connection method
AC
8 AWG (6-20
AWG)
3-pin terminal
block: L1
Line terminal: L1
Insert the wire into the
round opening and push
to clamp the wire.
3-pin terminal
block: L2
Line terminal: L2
3-pin terminal
block: N
Neutral terminal: N
Grounding
10 AWG cable
Grounding Bus-
bar
Grounding lug
Temperature Sensor
StorEdge Solution with Backup MAN-01-00262-1.5
68