Creating an Ethernet (LAN) Connection
This communication option enables using an Ethernet connection to connect the
inverter to the monitoring platform through a LAN.
Ethernet cable specifications:
Cable type – a shielded Ethernet cable (Cat5/5E STP) may be used
Maximum distance between the inverter and the router – 100 m/ 330 ft.
NOTE
If using a cable longer than 10 m / 33 ft in areas where there is
a risk of induced voltage surges by lightning, it is recommend
to use external surge protection devices.
For details refer to:
https://www.solaredge.com/sites/default/files/overvoltage_surge_
Figure 35: Example of Ethernet connection
Chapter 9: Setting Up Communication to the Monitoring Platform
101
StorEdge Solution with Backup MAN-01-00262-1.5