Main Inverter Status
Status
Inverter
SN 07318000C
Power
100 kW
Voltage
277 Vac
Frequency
60.9 Hz
P_OK: 138 of 141
Optimizers Connected
S_OK
Server Connected
Status
Production
Switch
OFF
CosPhi
1.00
Limit
No Limit
Country
Netherlands
Voltage
850 Vdc
Temp
20 C
Fan
OK
Switch Off. Production disabled
›
Commissioning
l
Inverter
: The inverter serial number
l
Power
: The AC output power
l
Voltage (Vac)
: The AC output voltage
l
Frequency
: The AC output frequency
l
P_OK: xxx of yyy:
There is a connection to the power optimizers and at least one power optimizer is
sending monitoring data. XXX is the number of power optimizers for which telemetries have been
received in the last two hours. YYY is the number of paired power optimizers identified during the
most recent pairing process. If XXX and YYY are not equal, there may be a problem in one or more
power optimizers.
l
S_OK
: The connection to the SolarEdge monitoring platform is successful (appears only if the inverter
is connected to the monitoring platform).
l
Status:
The inverter operation status: Off, Not Paired, Night Mode, Error, Pairing, or Production
l
Switch
: Indicates the position of the inverter ON/OFF/P switch: On, Off, or P position.
l
CosPhi
: Indicates the ratio between active and reactive power.A negative value indicates a lagging
CosPhi.
For more information, refer to the
Power Control Application Note
, available on the
SolarEdge website at
http://www.solaredge.com/files/pdfs/application_note_
power_control_configuration.pdf
l
Limit
: The inverter maximum output power
l
Country
: The selected country and grid setting
l
Voltage (Vdc)
: The DC input voltage
l
Temp
(°C or °F): The inverter heat sink temperature
Chapter 5: Activating, Commissioning and Configuring the System Using SolarEdge
Three Phase Inverter with synergy technology Guide MAN-01-00402-1.1
49