NETYS RT 5 - 7 - 9 - 11 kVA - 551570A - SOCOMEC
67
EN
Parallel the Socomec External Battery Packs
To extend the back-up time, you may parallel the Socomec external battery packs
before connecting them to the UPS. The two models’ parallel methods are similar.
For parallel application, only use the same type of Socomec external
battery packs (same product number).
1 Use the provided battery cable (
1
) to connect each parallel Socomec
external battery pack’s battery connector (
4
). Each Socomec external battery
pack has two identical battery connectors; you can choose either of them for
connection. Make sure that the positive cable (+) connects to the positive pole (+)
and the negative cable (-) connects to the negative pole (-). Use the screws (
2
)
and standoffs (
3
) (provided in the battery cable’s package) to fix the battery cable
firmly on the parallel
Socomec external battery packs. Please see
Figure 10-3
.
外接
电池
连接
孔
192
V D
C 5
0A
外接
电池
连接
孔
192
V D
C 5
0A
断路
器
250
V D
C 6
3A
外接
电池
连接
孔
192
V D
C 5
0A
断路
器
250
V D
C 6
3A
外接
电池
连接
孔
92V
DC
50
A
外接
电池
连接
孔
192
V D
C 5
0A
断路
器
250
V D
C 6
3A
外接
电池
连接
孔
192
V D
C 5
0A
断路
器
250
V D
C 6
3A
1
2
3
4
Socomec
External Battery
2
3
Packs
(Figure 10-3)
If you want to connect more than two Socomec external battery packs,
follow the steps mentioned above.
2 After paralleling the Socomec external battery packs, follow the steps
mentioned in ‘Connect the Socomec External Battery Pack the UPS’ to complete
the connection between the UPS and the parallel Socomec external battery packs.