NETYS RT 5 - 7 - 9 - 11 kVA - 551570A - SOCOMEC
18
EN
3.2. Multi-function Buttons
No.
Multi-
function
Button
Description
1
ON/ OFF
Button
The button has multiple functions. Please refer to the following
for detailed information.
1. Turn-on
In standby/ bypass mode, press and hold the button for 3 sec-
onds, release it after you hear one beep and the UPS will run in
on-line mode.
Cold start: When there is no AC input, press and hold the button
for 3 seconds, release it after you hear one beep and the UPS
will run in battery mode.
2. Turn-off
In on-line mode, (1) press and hold the button for 3
seconds, (2) release it after you hear one beep, (3) use the
Scrolling Up or Down button ( /
) to select 'Yes',
and (4) press the Enter button ( )
to confirm your selec-
tion. After that, the inverter will be off and the UPS will transfer to
run in standby or bypass mode.
The UPS will keep charging the batteries when the UPS is in
standby/ bypass mode. To fully turn off the UPS, it is advised to
disconnect the UPS from the AC power.
In battery mode, (1) press and hold the button for 3
seconds, (2) release it after you hear one beep, (3) use the
Scrolling Up or Down button (
/
) to select 'Yes',
and (4) press the Enter button (
) to confirm your selec-
tion. After that, the UPS will be turned off.
3. Fault Clear
When the UPS has a fault condition, press and hold the button
for 3 seconds, release it after you hear one beep and the UPS
will try to clear the fault condition.
2
ON/ OFF
Button
(Continued)
When the UPS clears the fault condition, it means that the
buzzer/ warning message has been turned off. To eliminate
the fault detected, please refer to
Chapter 11: Trouble
-
shooting
for relevant solutions.
The function mentioned above is only applicable to the
condition when the UPS has a fault situation and the
inverter is off.