NETYS RT 5 - 7 - 9 - 11 kVA - 551570A - SOCOMEC
26
EN
5. COMMUNICATION INTERFACES
The UPS can still function properly without making the connections below.
For the location of the following communication interfaces, please see
Figure 4-1
.
Communication software and accessories are available for monitoring the status
of the UPS, in order to optimize normal operation and ensure that shutdown at the
end of back-up time is managed correctly. Applications allow recording of all power
outages and any depletion of battery power so as to enable the activation of an
automatic procedure for closing programs in ordered sequence and shutting down
the system.
NETYS RT is equipped with RS232, RS485 and USB communication interfaces,
and slots for Web/SNMP cards.
5.1. Communication solutions
Local View, an ideal UPS monitoring and shutdown point-to-point solution for
Windows®, Linux® and Mac OS X® operating systems.
Web/SNMP manager (Web/SNMP slot card) allowing control via LAN using TCP/IP
protocol, and remote shutdown management.
BMS (JBUS-RS232 or RS485 interface), allows the UPS to interface with a Building
Management System.
5.2. Smart Slot
The smart slot is for option cards. You can install the SNMP or Relay I/O card in this slot
to let the system have network communication and dry contact functions.
5.3. Parallel Ports
The two parallel ports are for UPS parallel communication. UPS units (a maximum
of 2) with the same capacity, voltage and frequency can be coupled via the
provided parallel cable to run in parallel mode.
5.4. Dry Contacts
The NETYS RT UPS provides one input dry contact for you to receive external
control signals. You can set up relevant items in the Dry Contact Setting screen,
which includes Disable/ ROO/ RPO/ Remote shutdown/ Forced bypass/ On
generator. In addition, there are three configurable output dry contacts for you to
receive UPS events. The output dry contacts are normally open (NO). You can set
up relevant items in the Dry Contact Setting screen, which includes Disable/ On