Press and hold the button
for 3 seconds
and release it after you hear one beep.
In Progress...
Self Diagnosis
BYPS
231
V
PS
BATT
999 min
4 Once the UPS runs normally, switch on the output protective device (see
Figure
7-3
) installed between the UPS and the loads.
To prevent the UPS from activating the overload protection mechanism
during the start-up process, please turn on the high-power loads first and
then the low-power loads.
8.2. Single Unit Turn-off
1 Make sure all of the loads connected to the UPS are off.
2 (1) Press and hold the ON/ OFF button (
) for 3 seconds, (2) release it after
you hear one beep, (3) use the Scrolling Up or Down button (
/
) to select
'Yes', and (4) press the Enter button (
) to confirm your selection.
3 Switch off the input breaker, input protective device (see F
igure 7-3
) and output
protective devices (see
Figure 7-3
).
4 After the LCD backlight goes dim and the fans stop completely, switch off the
battery breaker to ensure that there is no remaining battery power.