REQUISITES
3.2 ENVIRONMENTAL REQUISITES.
• The UPS is not designed for outdoor use.
• Do not expose the UPS to direct sunlight or to sources of excessive heat.
• The recommended operating temperature, humidity and altitude values are listed in the technical specifi cations
table (see chapter 11). Cooling systems may be required to maintain these values.
• The UPS must be installed in an environment without obstructions and which is dry, clean and dust-free.
• Avoid dusty environments or areas where there is dust from conductive or corrosive materials (e.g. metal dust or
chemical solutions).
• The UPS can be installed against a wall; the distance will depend on the cables present. The upper part of the UPS
must be positioned at least 40 cm away from the ceiling (fi gure 3.2-1).
• The UPS switches are accessed from the front; however, a space of at least 1.5 metres should be left at the front of
the UPS for maintenance purposes (fi gura 3.2-1).
• For UPSs arranged frontally, leave a minimum space of 210 cm between the two cabinets so as to allow a pas-
sageway when both doors are open (in accordance with the provisions of standard IEC 60364 - see fi gure 3.2-1).
≥ 40 cm
≥ 210 cm
between the doors
MASTERYS
Green Power
MASTERYS
Green Power