Green Power
100-120 kVA
4
UNPACKING AND INSTALLATION
1. The filter level indicates:
1
immediate activation (1 seconds minimum communication time);
2
10 s delay;
3
30 s delay.
2. if the external E.S.D. button is not used, always insert a jumper to short circuit input IN 1.
11.1-1
OUT2
OUT3
IN1
IN3
OUT1
OUT4
IN1
IN2
4.7 ADC CARD WITH TEMPERATURE SENSOR.
This card can be used to manage up to four normally closed
or normally open outputs and up to three digital inputs in
confi gurable mode.
4.7.1 Electrical data of the contacts.
• 2 A 250 Vac, NO or NC depending on the terminal used.
• inputs: activated on loop closing.
Secure the card with the appropriate screws.
Mount the platic protection.
Description of signals
Message on mimic panel
General alarm
Battery discharging
Battery low and
imminent stop
UPS on bypass
E.S.D.
Supply from GenSet
Overheating
Description
Output contact “General Alarm”.
“Battery discharging” contact output.
“Battery low and imminent stop” contact output.
“UPS su bypass” contact output.
Contact input for Emergency Shutdown Device.
Generator ready signal input.
Internal overheating contact input.
No alarms.
C1
NO1
NC1
“General Alarm” active.
C1
NO1
NC1
Filter level
1
2
3
2
2
1
1
2
IN/OUT
Out 1
Out 2
Out 3
Out 4
In 1
2
In 2
In 3
Intervention of the E.S.D. input switches off the UPS output. To restore the UPS to operation:
• Close the E.S.D. contact on “In 1” on the ADC board.
• Give the reset alarms” command.
• Run the start procedure