ENGLISH
IOMMASGPXX00-GB_01
21
Green Power
100-120 kVA
UNPACKING AND INSTALLATION
4
4.4.4 Connecting THE BATTERY CABINET TEMPERATURE PROBE.
• SOCOMEC UPS battery cabinets:
- The SOCOMEC UPS battery cabinet comes with a temperature probe which must be connected to the card sup-
plied with the UPS (figure 4.4.4-1).
- Connect the temperature probe as shown in figure 4.4.4-2 without cabling distance limits and without the need
to observe polarity.
- In the event of a single UPS with several battery cabinets, use a single temperature sensor.
- In the event of parallel UPSs, connect the battery cabinet temperature sensors to the cards installed in the related
UPSs.
See paragraph 8.5.2 “Present configurations” menu”, BATTERY TEMP. SENSOR parameter.
4.4.4-2
OUT2
OUT3
IN1
OUT1
OUT4
IN1
IN2
IN3
IN3
IN3
4.4.4-1
OUT2
OUT3
IN1
IN3
OUT1
OUT4
IN1
IN2
temperature
temperature
probe
probe
• Other manufacturers’ battery cabinets:
- Use the specific kit available as an option.
- Fix the probe in the battery room or inside the battery cabinet.
- Connect the temperature probe as shown in figure 4.4.4-2 without cabling distance limits and without the need
to observe polarity, by using a 2x1 mm
2
double isolation cable.
- In the event of a single UPS with several battery cabinets, use a single temperature sensor.
- In the event of parallel UPSs, connect the battery cabinet temperature sensors to the cards installed in the related
UPSs.
Note.
If you do not intend to use the battery cabinet temperature sensor, go into the
SERVICE
>
SETTING
menu, select
the
BATT. TEMP. PROBE
parameter and set it to
DISABLE
.
WARNING!
If the BATT. TEMP. PROBE parameter is set to DISABLE, the battery-charger will not perform correc-
tion of the recharge voltage in function of the temperature.