IT
ALIANO
ENGLISH
58
IOMMASGPXX00-GB_01
Green Power
100-120 kVA
Intervention of the E.S.D. input switches off the UPS output.
To restore the UPS to operation:
• Close the E.S.D. contact on “In 1” on the ADC board.
• Give the reset alarms” command.
• Run the start procedure
OPTIONS
10
Description of signals
Message on the mimic panel
General Alarm
Battery Low or Imminent stop
E.S.D.
Supply from GenSet
Power safe plug 1
Power safe plug 2
Power safe plug 3
Management of energy consumption
E.S.D. activation
Over-heating
Overload/Loss of redundancy
Description
“General Alarm” contact output.
Battery low voltage and imminent shutdown contact output.
Contact input for emergency shutdown device.
Generator ready signal input.
Non privileged load 1 command output activated by overload or loss of redundancy.
Non privileged load 1 command output activated by battery discharging.
Non privileged load 1 command output activated by battery low.
Input for the battery to help providing energy in the event of peak consumption.
Shutdown for E.S.D. contact output.
Internal over-heating contact output.
Overload / loss of redundancy contact output
No alarm.
“General Alarm” active.
C1
NO1
NC1
C1
NO1
NC1
Summary of Contents for Green Power 100
Page 1: ...INSTALLATION AND OPERATING MANUAL Green Power 100 120 kVA ...
Page 2: ......
Page 64: ...FRANÇAIS ...