Green Power
100-120 kVA
MIMIC PANEL
6
6.2 MIMIC PANEL OVERVIEW.
UPPER BAR
(always displayed).
CLOCK
.
Hours and minutes.
The symbol “:” fl ashes once a second to indicate that the software is
running.
ALARMS AREA
.
Present when an alarm is active.
Press button DOWN to display the list of alarms.
See “Troubleshooting”.
Total output load (kVA).
Operating modes:
Normal (Normal mode), Eco (Eco-Mode mode), Auto (Automatic mode),
stdby (Standby program mode), e-saver (Energy Saver mode - parallel
confi gurations only), Service, Isolated (unit isolated from the electric
distribution plant).
Unit status:
Messages displayed: NOT POWERED, ON INVERTER, IMMINENT SHUT-
•
DOWN, FROM BATTERY, BATTERY TEST, ON MAINTENANCE BYPASS, ON
AUTO BYPASS, ON AUTO BYPASS, STARTING UPS..., SHUTTING DOWN UPS...,
UNIT AVAILABLE.
Priority of colours (from highest to lowest):
•
red: load not powered (on), shutdown imminent (fl ashing).
-
grey: when powering up or shutting down.
-
yellow: load powered off bypass or maintenance bypass in Battery Mode.
-
green: load powered off inverter or in ECO-MODE mode.
-
Mimic panel reference.