IT
ALIANO
ENGLISH
34
IOMMASGPXX00-GB_01
Green Power
100-120 kVA
6
MIMIC PANEL
SU INVERTER
UPS
Eco
1025kVA
10:30
?
6.1 GRAPHIC MIMIC PANEL.
The graphic mimic panel on the UPS door displays information regarding operating status, electrical measurements,
access to control functions and confi guration parameters. It includes a colour graphic display and a luminous status
bar, and provides access to:
mimic panel;
•
measurements, statuses and commands for the subassemblies;
•
programming battery tests and UPS operating modes;
•
assisted startup and switching to maintenance bypass procedures;
•
event and battery discharge log;
•
UPS and battery discharge duration statistics;
•
configuration menu;
•
list of states and alarms.
•
Display.
LEFT/RIGHT button.
Scrolls through the available
menus/pages to the right or left.
MENU buttons.
Access the respective displayed
menu.
Luminous status bar.
Refl ects the general status of the UPS.
The status bar colours are identical for both single and parallel UPS installations.
Green:
•
load protected by inverter (NORMAL mode);
-
load powered off automatic bypass (
-
ECO-MODE or ENERGY SAVER modes).
Green fl ashing: battery test in progress.
•
Yellow:
•
load powered off automatic bypass (NORMAL mode).
-
load powered off maintenance bypass;
-
Red:
•
on: load not powered;
-
fl ashing: imminent shutdown.
-
Off :
•
the UPS unit or module is isolated from the installation (Q2 or Q3 open)
-
automatic switch on or bypass procedure in progress.
-
USB port.
WARNING!
Do not connect devices
to the USB port. This can
damage the system.
ENTER button.
Accesses the currently displayed
menu, accept/send commands
and confi gurations to the UPS.
UP/DOWN button.
Scrolls up and down through
the available menus/values.