-50-
No.PF
※※
-OMA1007
To configure the pressure ramp up duration, hold the "S" button on the ITV until the display shows "F01"
and use the up and down arrows to select "F07". Press the "S" button once and edit the value. The value
displayed on the screen is seconds x10. Once the correct value has been selected press the "S" button to
set it.
Measurement mode
Press the SET button for 2 seconds.
Menu display
Press the UP button 4 times.
Menu display
Press the SET button.
Pressure ramp up duration
Press the UP or DOWN button to change the
setting.
Press the SET button.
Menu display
Press the SET button for 2 seconds.
Measurement mode
∗
: Refer to Operation Manual for "ITV#050-IL#-#-#-X399".