Definition and terminology
Term
Definition
A
Accumulated flow
The total amount of fluid that has passed through the device. If an instantaneous
flow of 100 L/min lasts for 5 minutes, the accumulated flow will be 5 x 100 = 500 L.
Accumulated-value hold time
A function to store the cumulative flow value in the product's internal memory at
certain time intervals. Reads the memory data when power is supplied.
Accumulation of data begins with the value read at the moment power is
supplied. The time interval for memorizing can be selected from 2 or 5 minutes.
AMS
Air Management System.
B
Base
A unit which establishes wireless communication of input or output data to the
remote. It is connected to a PLC to establish communication of input or output data.
Bottom value display (mode) Shows the min. from when the power was supplied to the current time.
Broken line detection
A broken wire to the input or output equipment has been detected by the
diagnostic function.
C
Chattering
The problem of the switch output turning ON and OFF repeatedly around the
set point value at high frequency due to the effect of pulsation.
Current consumption
Current which is necessary to operate each unit.
D
Delay time
•Standby ON Delay
The setting time from when the measured flow rate under standby flow
rate(threshold) to the set duration. If the standby input signal received and
Standby ON Delay time reached, the AMS change to standby mode.
•Standby OFF Delay
The setting time from when the measured flow rate exceeds standby flow
rate(threshold) to the set duration. When the AMS returns to Operation mode,
AMS shall be back to Standby mode without waiting for Standby ON Delay time.
DHCP
A protocol that automatically allocates information, necessary to be registered
to use the network, such as an IP address, to individual devices connected to
the TCP/IP network.
Digital filter
Function to add digital filtering to the fluctuation of the measured value. Smooth
the fluctuation of displayed value for sharp start up or fall of the flow and
pressure.
When the function is valid, digital filtering is reflected to the ON/OFF of the
switch output. The response time indicates when the set value is 90% in
relation to the step input.
Output chattering or flicker in the measurement mode display can be reduced
by setting the digital filter.
Display accuracy
Indicates the max. deviation between the displayed pressure value and the true
value.
Display colour
Indicates the color of the digital display.
Display value fine adjustment
(function)
Displayed pressure value can be adjusted within the range of ±5%R.D. (±5% of
displayed value). It is used if the true pressure value is known, or to eliminate
differences between the displayed values of different instruments that are
measuring the same pressure.
E
Enclosure (IP)
Abbreviation of International Protection. Standard related to protection against
extraneous matter, such as hand, steel ball, steel wire, dust particle or water,
applied to the product.
Error displayed
The error code number displayed, to identify the error detected by the self-
diagnostic function of the Air Management Hub.
Refer to the "Error display" on page