HSC960 Genset Controller User Manual
HSC960 Genset Controller Version:1.0 2015-05-21 Page 16 of 37
No.
Type
Description
14
Low Fuel Level
When the controller detects that the fuel level is lower than the set value
or there is Low Fuel Level input, it will initiate a shutdown alarm and the
alarm information will be displayed on the LCD.
15
Low Water
Level
When the controller detects that there is Low Water Level input, it will
initiate a shutdown alarm and the alarm information will be displayed on
the LCD.
16
Tem Sensor
Open
When the sen
sor didn‟t connect to correct port, it will initiate a shutdown
alarm and the alarm information will be displayed on the LCD.
17
Oil Sensor
Open
When the sensor didn‟t connect to correct port, it will initiate a shutdown
alarm and the alarm information will be displayed on the LCD.
18
Maintain Time
Over
When the genset working time has exceeded the maintain time,
moreover the maintain action has been set to shutdown, it will initiate a
shutdown alarm and the alarm information will be displayed on the LCD.
When the maintain action is negative, the alarm resets.
19
Tps Fail
When the Tps feedback signal failed, it will initiate a shutdown alarm and
the alarm information will be displayed on the LCD.
20
Aux. Sensor
Over
When the controller detects that the aux. sensor has exceeded the
pre-set value, it will initiate a shutdown alarm and the alarm information
will be displayed on the LCD.
21
Aux. Sensor
Under
When the controller detects that the aux. sensor has fallen below the
pre-set value, it will initiate a shutdown alarm and the alarm information
will be displayed on the LCD.