HSC960 Genset Controller User Manual
HSC960 Genset Controller Version:1.0 2015-05-21 Page 25 of 37
No
Items
Range
Default
Description
81
Idle Speed
(0-6000) r/min
900
Offer standard to adjust idle speed.
82
Idle Slope
0-6000
10
The rising speed rate during the
process of genset change idle running
status into rated speed running status.
83
Idle Gain
1-1000
500
The gain is regulated during the genset
is idle running.
84
Rated Speed
(0-6000) r/min
1500
Offer standard to adjust rated speed.
85
P Gain
1-3000
1100
The regulated gain when the genset is
running in rated speed.
86
I Gain
1-3000
35
87
D Gain
1-3000
1
88
Total Gain
1-1000
300
89
Window
(1-1000) r/min
200
90
Window Gain
1000-3000
1100
91
Position Gain
0-1000
0
92
Compensate Gain
0-100
0
93
P Gain(Position)
1-3000
1000
The regulated gain of throttle position.
94
I Gain(Position)
1-3000
300
95
D Gain(Position)
1-3000
100
96
Defined Curve Set (0-3)
0: Defined temperature sensor
1: Defined pressure sensor
2: Defined level sensor
3: Defined aux. sensor
Chose the sensor which needs setting,
then
input
resistance
value
and
corresponding value of each point. It
needs to input 8 points.
Note 1,
if “high temperature inhibit” is configured, or set auxiliary input as “inhibit high temperature stop” and
this input is active, when temperature is higher than the preset value, or high temperature alarm input is
active, controller will send warning signal only and not stop the unit.
Note 2,
if “low oil pressure inhibit” is configured, or set auxiliary input as “inhibit low oil pressure stop” and this
input is active, when oil pressure is lower than the preset value, or low oil pressure alarm input is active,
controller will send warning signal only and not stop the unit.
Note 3,
if “3P3W” is selected, maximum shutdown threshold of “Gens Over Voltage” can be set as 620V; when
select others, maximum shutdown threshold can be set as 360V.