HSC960 Genset Controller User Manual
HSC960 Genset Controller Version:1.0 2015-05-21 Page 27 of 37
Table 10-
Defined contents of configurable input ports (All active when connect to grand
(B-))
No
Items
Description
0
Not Used
1
High Temperature Input If these signals are active after safety on delay, shutdown alarm
will be immediately initiated.
2
Low Oil Pressure Input
3
Warn Input
Only warning and not shutdown if this input is active.
4
Shutdown input
Shutdown alarm will be immediately initiated if this input is
active.
5
WTH STOP by cool
When the genset is running normally and this signal is
activated, if there is a high temperature situation, the controller
will first cool down the generator and then stop it; if the signal is
deactivated and a high temperature situation occurs, the
controller will shut down the gen-set without cooling down.
6
Generator Closed input
7
Reserved
8
Inhibit
High
Temperature Stop
When it is active, high temperature shutdown will be prohibited.
9
Inhibit Low Oil Pressure
Stop
When it is active, low oil pressure shutdown will be prohibited.
10
Remote Start
11
Fuel Level Warn
12
Coolant Level Warn
13
Fuel Level Shutdown
14
Coolant Level Shutdown
15
Inhibit Start Auto
In Auto mode, if this input is active, whether remote start signal
activates or not, the controller will not give a start command to
the generator. If generator is normal running, stop command
won‟t be executed. When this input is deactivated, genset will
automatically start or stop.
16
Reserved