![Smartgen HSC960 User Manual Download Page 17](http://html1.mh-extra.com/html/smartgen/hsc960/hsc960_user-manual_1297545017.webp)
HSC960 Genset Controller User Manual
HSC960 Genset Controller Version:1.0 2015-05-21 Page 17 of 37
6
WIRINGS CONNECTION
Figure 2-
Back Panel
Table 7- Description of terminal connection
No.
Function
Cable
Size
Remarks
1
B-
2.5mm
2
Connected with negative of starter battery
2
B+
2.5 mm
2
Connected with positive of starter battery. Max.
20A fuse is recommended.
3
EM. Stop
2.5 mm
2
Connected with B+ via emergency stop button
4
Fuel
1.5 mm
2
Fuel relay output; B+ is supplied by 3 terminal;
rated 16A
5
Crank
1.5 mm
2
Start relay output; B+ is supplied by 3 terminal;
rated 16A; Connected to starter coil.
6
Aux. Output 1
1.5 mm
2
B+ is supplied by 2 terminal; rated 7A
7
Aux. Output 2
1.5 mm
2
Always close output; rated 7A;
8
1.5 mm
2
Common terminal
9
1.5 mm
2
Always open output; rated 7A;
10
Aux. Output 3
2.5 mm
2
Free contact always open; rated
7A; free contact output
Details see
Table 9
11
2.5 mm
2
12
Aux. Output 4
2.5 mm
2